Schneider ATV212H075N4 Variable Speed Drive ATV212 - 0.75kW
Optimize Your Motor Control with Schneider ATV212H075N4 Variable Speed Drive
The Schneider ATV212H075N4 is a top-tier variable speed drive designed specifically for HVAC applications, providing superior performance, energy efficiency, and operational versatility. This model, part of the reputable ATV212 series, delivers precise control for asynchronous motors up to 0.75 kW, making it an ideal choice for a range of industrial and commercial environments.
Key Features and Benefits
1. High Energy Efficiency:
- The ATV212H075N4 is engineered to maximize energy savings, with advanced motor control algorithms that optimize efficiency, particularly in HVAC systems. This drive can significantly reduce energy consumption, contributing to lower operational costs and a smaller carbon footprint.
2. Robust Performance:
- With its ability to handle up to 0.75 kW, the ATV212H075N4 ensures smooth and reliable operation under various load conditions. The drive features a high starting torque and precise speed regulation, ensuring consistent performance even in demanding applications.
3. Comprehensive Protection:
- The drive comes equipped with multiple protection features, including overcurrent, overvoltage, undervoltage, and thermal protection. These safeguards ensure the longevity and reliability of your motor, preventing damage and reducing maintenance costs.
4. Easy Integration and Configuration:
- The ATV212H075N4 is designed for seamless integration into existing systems. Its compact design and user-friendly interface simplify installation and configuration. The drive supports various communication protocols, making it adaptable to different control systems.
5. Enhanced Control Capabilities:
- Featuring advanced control functions such as PID regulation, multi-speed settings, and automatic restart, the ATV212H075N4 offers enhanced flexibility and control. These capabilities enable precise adjustment to match the specific requirements of your application.
6. Eco-Friendly Operation:
- Designed with sustainability in mind, the ATV212H075N4 complies with international energy standards and directives. Its efficient performance reduces environmental impact, aligning with green building and sustainability initiatives.
Technical Specifications
- Power Range: 0.75 kW
- Input Voltage: 380-480V AC
- Frequency Range: 50/60 Hz
- Control Type: Voltage/Frequency Control, Sensorless Vector Control
- Communication Protocols: Modbus, BACnet, Metasys N2, Apogee P1
- Operating Temperature: -10°C to +50°C
- Protection Class: IP20
- Dimensions (H x W x D): 260 x 130 x 150 mm
- Weight: 3.2 kg
Applications
The Schneider ATV212H075N4 is ideal for a wide range of HVAC applications, including:
- Air Handling Units (AHUs)
- Pumps and Fans
- Cooling Towers
- Compressors
- Heating, Ventilation, and Air Conditioning systems in commercial buildings
Why Choose Schneider Electric?
Schneider Electric is a global leader in energy management and automation. With a commitment to innovation and sustainability, Schneider offers cutting-edge solutions that enhance operational efficiency and reduce environmental impact. The ATV212H075N4 variable speed drive exemplifies this commitment, providing a reliable, efficient, and eco-friendly solution for your motor control needs.
Optimize your HVAC systems with the Schneider ATV212H075N4 Variable Speed Drive. Experience superior performance, energy efficiency, and reliability for your industrial and commercial applications.
range of product |
Altivar 212
|
|
---|---|---|
product or component type |
Variable speed drive
|
|
device short name |
ATV212
|
|
product destination |
Asynchronous motors
|
|
product specific application |
Pumps and fans in HVAC
|
|
assembly style |
With heat sink
|
|
network number of phases |
3 phases
|
|
motor power kW |
11 kW
|
|
motor power hp |
15 hp
|
|
[Us] rated supply voltage |
200...240 V - 15...10 %
|
|
supply voltage limits |
170...264 V
|
|
supply frequency |
50...60 Hz - 5...5 %
|
|
network frequency |
47.5...63 Hz
|
|
EMC filter |
Without EMC filter
|
|
line current |
34.4 A 240 V
42.1 A 200 V |
apparent power |
17.6 kVA 240 V
|
|
---|---|---|
prospective line Isc |
22 kA
|
|
continuous output current |
46.2 A 230 V
|
|
maximum transient current |
50.8 A 60 s
|
|
speed drive output frequency |
0.5...200 Hz
|
|
nominal switching frequency |
12 kHz
|
|
switching frequency |
12...16 kHz with derating factor
6...16 kHz adjustable |
|
speed range |
1...10
|
|
speed accuracy |
+/- 10 % of nominal slip 0.2 Tn to Tn
|
|
torque accuracy |
+/- 15 %
|
|
transient overtorque |
120 % of nominal motor torque +/- 10 % 60 s
|
|
asynchronous motor control profile |
Voltage/frequency ratio, 2 points
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Flux vector control without sensor, standard Voltage/frequency ratio, 5 points Voltage/frequency ratio - Energy Saving, quadratic U/f |
|
regulation loop |
Adjustable PI regulator
|
|
motor slip compensation |
Not available in voltage/frequency ratio motor control
Automatic whatever the load Adjustable |
|
local signalling |
1 LED red DC bus energized
|
|
output voltage |
<= power supply voltage
|
|
isolation |
Electrical between power and control
|
|
type of cable |
IEC cable without mounting kit 1 45 °C copper 90 °C XLPE/EPR
IEC cable without mounting kit 1 45 °C copper 70 °C PVC UL 508 cable with UL Type 1 kit 3 40 °C copper 75 °C PVC |
|
electrical connection |
Terminal 2.5 mm² AWG 14 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F,
R, RES
Terminal 25 mm² AWG 3 L1/R, L2/S, L3/T |
|
tightening torque |
4.5 N.m 40 lb.in L1/R, L2/S, L3/T
0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES |
|
supply |
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5
V DC +/- 5 % <= 10 A overload and short-circuit protection
Internal supply 24 V DC 21...27 V <= 200 A overload and short-circuit protection |
|
analogue input number |
2
|
|
analogue input type |
Switch-configurable voltage VIA 0...10 V DC 24 V max 30000 Ohm
10 bits
Configurable voltage VIB 0...10 V DC 24 V max 30000 Ohm 10 bits Configurable PTC probe VIB 0...6 probes 1500 Ohm Switch-configurable current VIA 0...20 mA 250 Ohm 10 bits |
|
sampling duration |
2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog |
|
response time |
2 ms +/- 0.5 ms FM analog
7 ms +/- 0.5 ms FLA, FLC discrete 7 ms +/- 0.5 ms FLB, FLC discrete 7 ms +/- 0.5 ms RY, RC discrete |
|
accuracy |
+/- 0.6 % VIA for a temperature variation 60 °C
+/- 0.6 % VIB for a temperature variation 60 °C +/- 1 % FM for a temperature variation 60 °C |
|
linearity error |
+/- 0.15 % of maximum value input VIA
+/- 0.15 % of maximum value input VIB +/- 0.2 % output FM |
|
analogue output number |
1
|
|
analogue output type |
Switch-configurable voltage FM 0...10 V DC 7620 Ohm 10 bits
Switch-configurable current FM 0...20 mA 970 Ohm 10 bits |
|
discrete output number |
2
|
|
discrete output type |
Configurable relay logic FLA, FLC NO 100000 cycles
Configurable relay logic FLB, FLC NC 100000 cycles Configurable relay logic RY, RC NO 100000 cycles |
|
minimum switching current |
3 mA 24 V DC configurable relay logic
|
|
maximum switching current |
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R |
|
discrete input type |
Programmable F 24 V DC level 1 PLC 4700 Ohm
Programmable R 24 V DC level 1 PLC 4700 Ohm Programmable RES 24 V DC level 1 PLC 4700 Ohm |
|
discrete input logic |
Positive logic (source) F, R, RES <= 5 V >= 11 V
Negative logic (sink) F, R, RES >= 16 V <= 10 V |
|
acceleration and deceleration ramps |
Linear adjustable separately from 0.01 to 3200 s
Automatic based on the load |
|
braking to standstill |
By DC injection
|
|
protection type |
Motor phase break motor
Break on the control circuit drive Thermal power stage drive Overvoltages on the DC bus drive Against exceeding limit speed drive Against input phase loss drive With PTC probes motor Input phase breaks drive Line supply overvoltage and undervoltage drive Line supply undervoltage drive Overcurrent between output phases and earth drive Overheating protection drive Short-circuit between motor phases drive Thermal protection motor |
|
dielectric strength |
2830 V DC between earth and power terminals
4230 V DC between control and power terminals |
|
insulation resistance |
>= 1 MOhm 500 V DC for 1 minute
|
|
frequency resolution |
0.024/50 Hz analog input
0.1 Hz display unit |
|
communication port protocol |
APOGEE FLN
METASYS N2 BACnet Modbus LonWorks |
|
connector type |
1 RJ45
1 open style |
|
physical interface |
2-wire RS 485
|
|
transmission frame |
RTU
|
|
transmission rate |
9600 bps or 19200 bps
|
|
data format |
8 bits, 1 stop, odd even or no configurable parity
|
|
type of polarization |
No impedance
|
|
number of addresses |
1...247
|
|
communication service |
Monitoring inhibitable
Read holding registers (03) 2 words maximum Read device identification (43) Write multiple registers (16) 2 words maximum Time out setting from 0.1 to 100 s Write single register (06) |
|
option card |
Communication card LonWorks
|
|
operating position |
Vertical +/- 10 degree
|
|
width |
245 mm
|
|
height |
330 mm
|
|
depth |
190 mm
|
|
product weight |
11.55 kg
|
|
power dissipation in W |
459 W
|
|
air flow |
157 m3/h
|
|
specific application |
HVAC
|
|
IP degree of protection |
IP21
|
|
Variable speed drive application selection |
Building - HVAC : compressor for scroll
Building - HVAC : fan Building - HVAC : pump |
|
Motor power range AC-3 |
7...11 kW at 200...240 V 3 phases
|
|
motor starter type |