Schneider ATV212H075N4 Variable Speed Drive ATV212 - 0.75kW
  • Brand: Schneider
  • Product Code: ATV212H075N4
1000 |

Ex Tax: $0.00
Loading...

Description

Schneider ATV212H075N4 Variable Speed Drive ATV212 - 0.75kW

Optimize Your Motor Control with Schneider ATV212H075N4 Variable Speed Drive

The Schneider ATV212H075N4 is a top-tier variable speed drive designed specifically for HVAC applications, providing superior performance, energy efficiency, and operational versatility. This model, part of the reputable ATV212 series, delivers precise control for asynchronous motors up to 0.75 kW, making it an ideal choice for a range of industrial and commercial environments.

Key Features and Benefits

1. High Energy Efficiency:

  • The ATV212H075N4 is engineered to maximize energy savings, with advanced motor control algorithms that optimize efficiency, particularly in HVAC systems. This drive can significantly reduce energy consumption, contributing to lower operational costs and a smaller carbon footprint.

2. Robust Performance:

  • With its ability to handle up to 0.75 kW, the ATV212H075N4 ensures smooth and reliable operation under various load conditions. The drive features a high starting torque and precise speed regulation, ensuring consistent performance even in demanding applications.

3. Comprehensive Protection:

  • The drive comes equipped with multiple protection features, including overcurrent, overvoltage, undervoltage, and thermal protection. These safeguards ensure the longevity and reliability of your motor, preventing damage and reducing maintenance costs.

4. Easy Integration and Configuration:

  • The ATV212H075N4 is designed for seamless integration into existing systems. Its compact design and user-friendly interface simplify installation and configuration. The drive supports various communication protocols, making it adaptable to different control systems.

5. Enhanced Control Capabilities:

  • Featuring advanced control functions such as PID regulation, multi-speed settings, and automatic restart, the ATV212H075N4 offers enhanced flexibility and control. These capabilities enable precise adjustment to match the specific requirements of your application.

6. Eco-Friendly Operation:

  • Designed with sustainability in mind, the ATV212H075N4 complies with international energy standards and directives. Its efficient performance reduces environmental impact, aligning with green building and sustainability initiatives.

Technical Specifications

  • Power Range: 0.75 kW
  • Input Voltage: 380-480V AC
  • Frequency Range: 50/60 Hz
  • Control Type: Voltage/Frequency Control, Sensorless Vector Control
  • Communication Protocols: Modbus, BACnet, Metasys N2, Apogee P1
  • Operating Temperature: -10°C to +50°C
  • Protection Class: IP20
  • Dimensions (H x W x D): 260 x 130 x 150 mm
  • Weight: 3.2 kg

Applications

The Schneider ATV212H075N4 is ideal for a wide range of HVAC applications, including:

  • Air Handling Units (AHUs)
  • Pumps and Fans
  • Cooling Towers
  • Compressors
  • Heating, Ventilation, and Air Conditioning systems in commercial buildings

Why Choose Schneider Electric?

Schneider Electric is a global leader in energy management and automation. With a commitment to innovation and sustainability, Schneider offers cutting-edge solutions that enhance operational efficiency and reduce environmental impact. The ATV212H075N4 variable speed drive exemplifies this commitment, providing a reliable, efficient, and eco-friendly solution for your motor control needs.

Optimize your HVAC systems with the Schneider ATV212H075N4 Variable Speed Drive. Experience superior performance, energy efficiency, and reliability for your industrial and commercial applications.

Main
range of product
Altivar 212
product or component type
Variable speed drive
device short name
ATV212
product destination
Asynchronous motors
product specific application
Pumps and fans in HVAC
assembly style
With heat sink
network number of phases
3 phases
motor power kW
11 kW
motor power hp
15 hp
[Us] rated supply voltage
200...240 V - 15...10 %
supply voltage limits
170...264 V
supply frequency
50...60 Hz - 5...5 %
network frequency
47.5...63 Hz
EMC filter
Without EMC filter
line current
34.4 A 240 V
42.1 A 200 V
Complementary
apparent power
17.6 kVA 240 V
prospective line Isc
22 kA
continuous output current
46.2 A 230 V
maximum transient current
50.8 A 60 s
speed drive output frequency
0.5...200 Hz
nominal switching frequency
12 kHz
switching frequency
12...16 kHz with derating factor
6...16 kHz adjustable
speed range
1...10
speed accuracy
+/- 10 % of nominal slip 0.2 Tn to Tn
torque accuracy
+/- 15 %
transient overtorque
120 % of nominal motor torque +/- 10 % 60 s
asynchronous motor control profile
Voltage/frequency ratio, 2 points
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Flux vector control without sensor, standard
Voltage/frequency ratio, 5 points
Voltage/frequency ratio - Energy Saving, quadratic U/f
regulation loop
Adjustable PI regulator
motor slip compensation
Not available in voltage/frequency ratio motor control
Automatic whatever the load
Adjustable
local signalling
1 LED red DC bus energized
output voltage
<= power supply voltage
isolation
Electrical between power and control
type of cable
IEC cable without mounting kit 1 45 °C copper 90 °C XLPE/EPR
IEC cable without mounting kit 1 45 °C copper 70 °C PVC
UL 508 cable with UL Type 1 kit 3 40 °C copper 75 °C PVC
electrical connection
Terminal 2.5 mm² AWG 14 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES
Terminal 25 mm² AWG 3 L1/R, L2/S, L3/T
tightening torque
4.5 N.m 40 lb.in L1/R, L2/S, L3/T
0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES
supply
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 % <= 10 A overload and short-circuit protection
Internal supply 24 V DC 21...27 V <= 200 A overload and short-circuit protection
analogue input number
2
analogue input type
Switch-configurable voltage VIA 0...10 V DC 24 V max 30000 Ohm 10 bits
Configurable voltage VIB 0...10 V DC 24 V max 30000 Ohm 10 bits
Configurable PTC probe VIB 0...6 probes 1500 Ohm
Switch-configurable current VIA 0...20 mA 250 Ohm 10 bits
sampling duration
2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog
response time
2 ms +/- 0.5 ms FM analog
7 ms +/- 0.5 ms FLA, FLC discrete
7 ms +/- 0.5 ms FLB, FLC discrete
7 ms +/- 0.5 ms RY, RC discrete
accuracy
+/- 0.6 % VIA for a temperature variation 60 °C
+/- 0.6 % VIB for a temperature variation 60 °C
+/- 1 % FM for a temperature variation 60 °C
linearity error
+/- 0.15 % of maximum value input VIA
+/- 0.15 % of maximum value input VIB
+/- 0.2 % output FM
analogue output number
1
analogue output type
Switch-configurable voltage FM 0...10 V DC 7620 Ohm 10 bits
Switch-configurable current FM 0...20 mA 970 Ohm 10 bits
discrete output number
2
discrete output type
Configurable relay logic FLA, FLC NO 100000 cycles
Configurable relay logic FLB, FLC NC 100000 cycles
Configurable relay logic RY, RC NO 100000 cycles
minimum switching current
3 mA 24 V DC configurable relay logic
maximum switching current
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R
2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R
2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R
discrete input type
Programmable F 24 V DC level 1 PLC 4700 Ohm
Programmable R 24 V DC level 1 PLC 4700 Ohm
Programmable RES 24 V DC level 1 PLC 4700 Ohm
discrete input logic
Positive logic (source) F, R, RES <= 5 V >= 11 V
Negative logic (sink) F, R, RES >= 16 V <= 10 V
acceleration and deceleration ramps
Linear adjustable separately from 0.01 to 3200 s
Automatic based on the load
braking to standstill
By DC injection
protection type
Motor phase break motor
Break on the control circuit drive
Thermal power stage drive
Overvoltages on the DC bus drive
Against exceeding limit speed drive
Against input phase loss drive
With PTC probes motor
Input phase breaks drive
Line supply overvoltage and undervoltage drive
Line supply undervoltage drive
Overcurrent between output phases and earth drive
Overheating protection drive
Short-circuit between motor phases drive
Thermal protection motor
dielectric strength
2830 V DC between earth and power terminals
4230 V DC between control and power terminals
insulation resistance
>= 1 MOhm 500 V DC for 1 minute
frequency resolution
0.024/50 Hz analog input
0.1 Hz display unit
communication port protocol
APOGEE FLN
METASYS N2
BACnet
Modbus
LonWorks
connector type
1 RJ45
1 open style
physical interface
2-wire RS 485
transmission frame
RTU
transmission rate
9600 bps or 19200 bps
data format
8 bits, 1 stop, odd even or no configurable parity
type of polarization
No impedance
number of addresses
1...247
communication service
Monitoring inhibitable
Read holding registers (03) 2 words maximum
Read device identification (43)
Write multiple registers (16) 2 words maximum
Time out setting from 0.1 to 100 s
Write single register (06)
option card
Communication card LonWorks
operating position
Vertical +/- 10 degree
width
245 mm
height
330 mm
depth
190 mm
product weight
11.55 kg
power dissipation in W
459 W
air flow
157 m3/h
specific application
HVAC
IP degree of protection
IP21
Variable speed drive application selection
Building - HVAC : compressor for scroll
Building - HVAC : fan
Building - HVAC : pump
Motor power range AC-3
7...11 kW at 200...240 V 3 phases
motor starter type
Variable speed drive