Schneider ATV212HD15N4 Variable Speed Drive – 15kW
Optimize your industrial operations with the Schneider ATV212HD15N4 Variable Speed Drive, engineered for performance and efficiency. This advanced drive belongs to Schneider Electric's ATV212 series, renowned for its robustness and versatility in controlling asynchronous motors.
Key Features:
- Power Rating: The ATV212HD15N4 offers a substantial 15kW power capacity, making it ideal for medium to large-scale applications that demand reliable and precise motor control.
- Variable Speed Control: Achieve optimal performance with its sophisticated variable speed control, providing seamless adjustments to motor speed and torque. This feature enhances the efficiency of your machinery, reduces energy consumption, and extends equipment lifespan.
- High Performance: With a maximum output frequency of up to 400 Hz, this drive ensures smooth and reliable motor operation across a wide range of speeds.
- Robust Design: Designed to withstand harsh industrial environments, the ATV212HD15N4 features a durable construction that ensures long-term reliability and minimal maintenance.
- User-Friendly Interface: The intuitive control panel and programmable functions offer ease of use, allowing for quick setup and adjustments tailored to your specific application needs.
- Energy Efficiency: Incorporates advanced energy-saving technology that optimizes power usage, contributing to reduced operational costs and a lower environmental footprint.
- Flexible Connectivity: Equipped with a range of communication options, including Modbus, to facilitate integration with existing systems and enhance operational flexibility.
Applications:
The Schneider ATV212HD15N4 is versatile and suitable for a variety of applications, including:
- HVAC systems
- Water and wastewater treatment
- Pump and fan control
- Conveyor systems
- Industrial machinery
Why Choose Schneider ATV212HD15N4?
Schneider Electric's commitment to innovation and quality is evident in the ATV212HD15N4 Variable Speed Drive. Its superior performance, reliability, and advanced features make it a valuable component in optimizing your industrial processes. Whether you’re upgrading existing systems or implementing new solutions, this drive provides the efficiency and control needed to meet today’s demanding industrial standards.
Specifications:
- Model: ATV212HD15N4
- Power Rating: 15kW
- Voltage Range: 380-480V
- Frequency Range: 0-400 Hz
- Communication Protocols: Modbus, others
- Enclosure Rating: IP20
Enhance your industrial automation with the Schneider ATV212HD15N4 Variable Speed Drive. For detailed information and to place an order, contact us today.
range of product |
Altivar 212
|
|
---|---|---|
product or component type |
Variable speed drive
|
|
device short name |
ATV212
|
|
product destination |
Asynchronous motors
|
|
product specific application |
Pumps and fans in HVAC
|
|
assembly style |
With heat sink
|
|
network number of phases |
3 phases
|
|
motor power kW |
11 kW
|
|
motor power hp |
15 hp
|
|
[Us] rated supply voltage |
200...240 V - 15...10 %
|
|
supply voltage limits |
170...264 V
|
|
supply frequency |
50...60 Hz - 5...5 %
|
|
network frequency |
47.5...63 Hz
|
|
EMC filter |
Without EMC filter
|
|
line current |
34.4 A 240 V
42.1 A 200 V |
apparent power |
17.6 kVA 240 V
|
|
---|---|---|
prospective line Isc |
22 kA
|
|
continuous output current |
46.2 A 230 V
|
|
maximum transient current |
50.8 A 60 s
|
|
speed drive output frequency |
0.5...200 Hz
|
|
nominal switching frequency |
12 kHz
|
|
switching frequency |
12...16 kHz with derating factor
6...16 kHz adjustable |
|
speed range |
1...10
|
|
speed accuracy |
+/- 10 % of nominal slip 0.2 Tn to Tn
|
|
torque accuracy |
+/- 15 %
|
|
transient overtorque |
120 % of nominal motor torque +/- 10 % 60 s
|
|
asynchronous motor control profile |
Voltage/frequency ratio, 2 points
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Flux vector control without sensor, standard Voltage/frequency ratio, 5 points Voltage/frequency ratio - Energy Saving, quadratic U/f |
|
regulation loop |
Adjustable PI regulator
|
|
motor slip compensation |
Not available in voltage/frequency ratio motor control
Automatic whatever the load Adjustable |
|
local signalling |
1 LED red DC bus energized
|
|
output voltage |
<= power supply voltage
|
|
isolation |
Electrical between power and control
|
|
type of cable |
IEC cable without mounting kit 1 45 °C copper 90 °C XLPE/EPR
IEC cable without mounting kit 1 45 °C copper 70 °C PVC UL 508 cable with UL Type 1 kit 3 40 °C copper 75 °C PVC |
|
electrical connection |
Terminal 2.5 mm² AWG 14 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F,
R, RES
Terminal 25 mm² AWG 3 L1/R, L2/S, L3/T |
|
tightening torque |
4.5 N.m 40 lb.in L1/R, L2/S, L3/T
0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES |
|
supply |
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5
V DC +/- 5 % <= 10 A overload and short-circuit protection
Internal supply 24 V DC 21...27 V <= 200 A overload and short-circuit protection |
|
analogue input number |
2
|
|
analogue input type |
Switch-configurable voltage VIA 0...10 V DC 24 V max 30000 Ohm
10 bits
Configurable voltage VIB 0...10 V DC 24 V max 30000 Ohm 10 bits Configurable PTC probe VIB 0...6 probes 1500 Ohm Switch-configurable current VIA 0...20 mA 250 Ohm 10 bits |
|
sampling duration |
2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog |
|
response time |
2 ms +/- 0.5 ms FM analog
7 ms +/- 0.5 ms FLA, FLC discrete 7 ms +/- 0.5 ms FLB, FLC discrete 7 ms +/- 0.5 ms RY, RC discrete |
|
accuracy |
+/- 0.6 % VIA for a temperature variation 60 °C
+/- 0.6 % VIB for a temperature variation 60 °C +/- 1 % FM for a temperature variation 60 °C |
|
linearity error |
+/- 0.15 % of maximum value input VIA
+/- 0.15 % of maximum value input VIB +/- 0.2 % output FM |
|
analogue output number |
1
|
|
analogue output type |
Switch-configurable voltage FM 0...10 V DC 7620 Ohm 10 bits
Switch-configurable current FM 0...20 mA 970 Ohm 10 bits |
|
discrete output number |
2
|
|
discrete output type |
Configurable relay logic FLA, FLC NO 100000 cycles
Configurable relay logic FLB, FLC NC 100000 cycles Configurable relay logic RY, RC NO 100000 cycles |
|
minimum switching current |
3 mA 24 V DC configurable relay logic
|
|
maximum switching current |
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R |
|
discrete input type |
Programmable F 24 V DC level 1 PLC 4700 Ohm
Programmable R 24 V DC level 1 PLC 4700 Ohm Programmable RES 24 V DC level 1 PLC 4700 Ohm |
|
discrete input logic |
Positive logic (source) F, R, RES <= 5 V >= 11 V
Negative logic (sink) F, R, RES >= 16 V <= 10 V |
|
acceleration and deceleration ramps |
Linear adjustable separately from 0.01 to 3200 s
Automatic based on the load |
|
braking to standstill |
By DC injection
|
|
protection type |
Motor phase break motor
Break on the control circuit drive Thermal power stage drive Overvoltages on the DC bus drive Against exceeding limit speed drive Against input phase loss drive With PTC probes motor Input phase breaks drive Line supply overvoltage and undervoltage drive Line supply undervoltage drive Overcurrent between output phases and earth drive Overheating protection drive Short-circuit between motor phases drive Thermal protection motor |
|
dielectric strength |
2830 V DC between earth and power terminals
4230 V DC between control and power terminals |
|
insulation resistance |
>= 1 MOhm 500 V DC for 1 minute
|
|
frequency resolution |
0.024/50 Hz analog input
0.1 Hz display unit |
|
communication port protocol |
APOGEE FLN
METASYS N2 BACnet Modbus LonWorks |
|
connector type |
1 RJ45
1 open style |
|
physical interface |
2-wire RS 485
|
|
transmission frame |
RTU
|
|
transmission rate |
9600 bps or 19200 bps
|
|
data format |
8 bits, 1 stop, odd even or no configurable parity
|
|
type of polarization |
No impedance
|
|
number of addresses |
1...247
|
|
communication service |
Monitoring inhibitable
Read holding registers (03) 2 words maximum Read device identification (43) Write multiple registers (16) 2 words maximum Time out setting from 0.1 to 100 s Write single register (06) |
|
option card |
Communication card LonWorks
|
|
operating position |
Vertical +/- 10 degree
|
|
width |
245 mm
|
|
height |
330 mm
|
|
depth |
190 mm
|
|
product weight |
11.55 kg
|
|
power dissipation in W |
459 W
|
|
air flow |
157 m3/h
|
|
specific application |
HVAC
|
|
IP degree of protection |
IP21
|
|
Variable speed drive application selection |
Building - HVAC : compressor for scroll
Building - HVAC : fan Building - HVAC : pump |
|
Motor power range AC-3 |
7...11 kW at 200...240 V 3 phases
|
|
motor starter type |
Variable speed drive
|
Schneider ATV212HD15N4 Variable Speed Drive - 15kW
- Brand: Schneider
- Product Code: ATV212HD15N4
- Availability: 1000
Tags: Schneider, ATV212HD15N4, Variable Speed Drive, 15kW, Schneider Electric, Industrial Drive, Motor Control, High Performance Drive, Energy Efficient, Variable Frequency Drive, HVAC Drive, Pump Control