Schneider ATV212WD37N4C Variable Speed Drive - 37kW
Optimize Your Motor Control with Precision and Reliability
The Schneider ATV212WD37N4C Variable Speed Drive is engineered to deliver exceptional performance and versatility for your industrial automation needs. With a robust 37kW power rating, this advanced drive is designed to enhance operational efficiency and energy savings for a wide range of applications.
Key Features:
High Power Output: The ATV212WD37N4C is rated for 37kW, providing reliable and efficient control for high-power motor applications. Whether you’re managing conveyor systems, pumps, or fans, this drive ensures optimal performance.
Advanced Control Technology: Featuring sophisticated control algorithms, the ATV212WD37N4C enables precise speed and torque management. Its advanced control technology enhances process accuracy and reduces mechanical stress on your equipment.
Enhanced Energy Efficiency: Designed with energy-saving capabilities, this variable speed drive minimizes power consumption and operating costs. It adjusts motor speed in real-time based on load requirements, optimizing energy use and reducing overall expenses.
User-Friendly Interface: The drive comes with an intuitive operator interface, allowing for easy setup and configuration. The clear display and straightforward controls simplify adjustments and monitoring, making it accessible for both experienced engineers and newcomers.
Robust Protection: The ATV212WD37N4C includes comprehensive protection features to safeguard your investment. It offers overcurrent, overvoltage, and thermal protection to ensure reliable operation even under demanding conditions.
Flexible Integration: With its versatile communication options, the ATV212WD37N4C integrates seamlessly with existing automation systems. It supports various protocols, enabling smooth connectivity and control across different platforms.
Durable Construction: Built to withstand harsh industrial environments, this drive features a rugged design that ensures longevity and durability. Its high-quality construction resists dust, moisture, and temperature fluctuations.
Regulatory Compliance: The ATV212WD37N4C meets stringent international standards, ensuring safety and reliability in diverse applications. It complies with CE, UL, and other regulatory certifications.
Applications:
The Schneider ATV212WD37N4C Variable Speed Drive is ideal for a variety of industrial applications, including:
- Conveyor systems
- Pumps and fans
- HVAC systems
- Water treatment plants
- Material handling systems
Why Choose Schneider ATV212WD37N4C?
- Exceptional Performance: Achieve superior control and efficiency with Schneider’s cutting-edge drive technology.
- Energy Savings: Reduce operational costs with advanced energy management features.
- Ease of Use: Simplify setup and operation with a user-friendly interface.
- Reliability: Trust in Schneider’s reputation for high-quality, durable products.
Elevate your industrial automation with the Schneider ATV212WD37N4C Variable Speed Drive. Contact us today to learn more about how this powerful drive can enhance your operations.
range of product |
Altivar 212
|
|
---|---|---|
product or component type |
Variable speed drive
|
|
device short name |
ATV212
|
|
product destination |
Asynchronous motors
|
|
product specific application |
Pumps and fans in HVAC
|
|
assembly style |
With heat sink
|
|
network number of phases |
3 phases
|
|
motor power kW |
22 kW
|
|
motor power hp |
30 hp
|
|
[Us] rated supply voltage |
380...480 V - 15...10 %
|
|
supply voltage limits |
323...528 V
|
|
supply frequency |
50...60 Hz - 5...5 %
|
|
network frequency |
47.5...63 Hz
|
|
EMC filter |
Class C1 EMC filter integrated
|
|
line current |
33.1 A 480 V
41.1 A 380 V |
apparent power |
33.2 kVA 380 V
|
|
---|---|---|
prospective line Isc |
22 kA
|
|
continuous output current |
43.5 A 380 V
43.5 A 460 V |
|
maximum transient current |
47.9 A 60 s
|
|
speed drive output frequency |
0.5...200 Hz
|
|
nominal switching frequency |
8 kHz
|
|
switching frequency |
6...16 kHz adjustable
8...16 kHz with derating factor |
|
speed range |
1...10
|
|
speed accuracy |
+/- 10 % of nominal slip 0.2 Tn to Tn
|
|
torque accuracy |
+/- 15 %
|
|
transient overtorque |
120 % of nominal motor torque +/- 10 % 60 s
|
|
asynchronous motor control profile |
Voltage/frequency ratio, 2 points
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor, standard Voltage/frequency ratio, 5 points |
|
regulation loop |
Adjustable PI regulator
|
|
motor slip compensation |
Not available in voltage/frequency ratio motor control
Automatic whatever the load Adjustable |
|
local signalling |
1 LED red DC bus energized
|
|
output voltage |
<= power supply voltage
|
|
isolation |
Electrical between power and control
|
|
type of cable |
IEC cable without mounting kit 1 45 °C copper 90 °C XLPE/EPR
IEC cable without mounting kit 1 45 °C copper 70 °C PVC UL 508 cable with UL Type 1 kit 3 40 °C copper 75 °C PVC |
|
electrical connection |
Terminal 2.5 mm² AWG 14 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F,
R, RES
Terminal 25 mm² AWG 3 L1/R, L2/S, L3/T Terminal 50 mm² AWG 1/0 U/T1, V/T2, W/T3 |
|
tightening torque |
4.3 N.m 38 lb.in L1/R, L2/S, L3/T
24 N.m 212 lb.in U/T1, V/T2, W/T3 0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES |
|
supply |
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5
V DC +/- 5 % <= 10 A overload and short-circuit protection
Internal supply 24 V DC 21...27 V <= 200 A overload and short-circuit protection |
|
analogue input number |
2
|
|
analogue input type |
Switch-configurable voltage VIA 0...10 V DC 24 V max 30000 Ohm
10 bits
Configurable voltage VIB 0...10 V DC 24 V max 30000 Ohm 10 bits Configurable PTC probe VIB 0...6 probes 1500 Ohm Switch-configurable current VIA 0...20 mA 250 Ohm 10 bits |
|
sampling duration |
2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog |
|
response time |
2 ms +/- 0.5 ms FM analog
7 ms +/- 0.5 ms FLA, FLC discrete 7 ms +/- 0.5 ms FLB, FLC discrete 7 ms +/- 0.5 ms RY, RC discrete |
|
accuracy |
+/- 0.6 % VIA for a temperature variation 60 °C
+/- 0.6 % VIB for a temperature variation 60 °C +/- 1 % FM for a temperature variation 60 °C |
|
linearity error |
+/- 0.15 % of maximum value input VIA
+/- 0.15 % of maximum value input VIB +/- 0.2 % output FM |
|
analogue output number |
1
|
|
analogue output type |
Switch-configurable voltage FM 0...10 V DC 7620 Ohm 10 bits
Switch-configurable current FM 0...20 mA 970 Ohm 10 bits |
|
discrete output number |
2
|
|
discrete output type |
Configurable relay logic FLA, FLC NO 100000 cycles
Configurable relay logic FLB, FLC NC 100000 cycles Configurable relay logic RY, RC NO 100000 cycles |
|
minimum switching current |
3 mA 24 V DC configurable relay logic
|
|
maximum switching current |
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R |
|
discrete input type |
Programmable F 24 V DC level 1 PLC 4700 Ohm
Programmable R 24 V DC level 1 PLC 4700 Ohm Programmable RES 24 V DC level 1 PLC 4700 Ohm |
|
discrete input logic |
Positive logic (source) F, R, RES <= 5 V >= 11 V
Negative logic (sink) F, R, RES >= 16 V <= 10 V |
|
acceleration and deceleration ramps |
Linear adjustable separately from 0.01 to 3200 s
Automatic based on the load |
|
braking to standstill |
By DC injection
|
|
protection type |
Motor phase break motor
Break on the control circuit drive Thermal power stage drive Overvoltages on the DC bus drive Against exceeding limit speed drive Against input phase loss drive With PTC probes motor Input phase breaks drive Line supply overvoltage and undervoltage drive Line supply undervoltage drive Overcurrent between output phases and earth drive Overheating protection drive Short-circuit between motor phases drive Thermal protection motor |
|
dielectric strength |
3535 V DC between earth and power terminals
5092 V DC between control and power terminals |
|
insulation resistance |
>= 1 MOhm 500 V DC for 1 minute
|
|
frequency resolution |
0.024/50 Hz analog input
0.1 Hz display unit |
|
communication port protocol |
LonWorks
METASYS N2 APOGEE FLN BACnet Modbus |
|
connector type |
1 open style
1 RJ45 |
|
physical interface |
2-wire RS 485
|
|
transmission frame |
RTU
|
|
transmission rate |
9600 bps or 19200 bps
|
|
data format |
8 bits, 1 stop, odd even or no configurable parity
|
|
type of polarization |
No impedance
|
|
number of addresses |
1...247
|
|
communication service |
Read holding registers (03) 2 words maximum
Read device identification (43) Monitoring inhibitable Write multiple registers (16) 2 words maximum Write single register (06) Time out setting from 0.1 to 100 s |
|
option card |
Communication card LonWorks
|
|
operating position |
Vertical +/- 10 degree
|
|
width |
284 mm
|
|
height |
720 mm
|
|
depth |
315 mm
|
|
product weight |
58.5 kg
|
|
specific application |
HVAC
|
|
IP degree of protection |
IP55
|
electromagnetic compatibility |
Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Voltage dips and interruptions immunity test IEC 61000-4-11 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 Electrostatic discharge immunity test level 3 IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 |
|
---|---|---|
pollution degree |
3 IEC 61800-5-1
|
|
IP degree of protection |
IP55 EN/IEC 61800-5-1
IP55 EN/IEC 60529 |
|
vibration resistance |
1 gn 13...200 Hz EN/IEC 60068-2-8
1.5 mm 3...13 Hz EN/IEC 60068-2-6 |
|
shock resistance |
15 gn 11 ms IEC 60068-2-27
|
|
environmental characteristic |
Classes 3C1 IEC 60721-3-3
Classes 3S2 IEC 60721-3-3 |
|
noise level |
59.9 dB 86/188/EEC
|
|
operating altitude |
1000...3000 m limited to 2000 m for the Corner Grounded
distribution network with current derating 1 % per 100 m
<= 1000 m without derating |
|
relative humidity |
5...95 % without condensation IEC 60068-2-3
5...95 % without dripping water IEC 60068-2-3 |
|
ambient air temperature for operation |
-10...40 °C without derating
> 40...50 °C with derating factor |
|
ambient air temperature for storage |
-25...70 °C
|
|
standards |
EN 61800-3 environments 2 category C3
EN 61800-5-1 IEC 61800-3 IEC 61800-3 environments 2 category C3 EN 55011 group 1 class B IEC 61800-3 category C1 EN 61800-3 environments 2 category C2 EN 61800-3 environments 1 category C2 EN 61800-3 category C1 EN 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C1 EN 61800-3 EN 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 1 category C2 IEC 61800-5-1 |
|
product certifications |
UL
CSA NOM 117 C-Tick |
|
marking |
CE
|