Schneider ATV9B0C16T6 Variable Speed Drive Altivar Process Modular, ATV900, Low Harmonic/Regen Drive
Overview: The Schneider ATV9B0C16T6 Variable Speed Drive is part of the advanced Altivar Process ATV900 series, designed for the most demanding industrial applications. This 160 kW drive offers unparalleled performance with integrated low harmonic and regenerative capabilities, making it an ideal solution for industries focused on energy efficiency, operational precision, and sustainability. Engineered to handle complex processes, the ATV9B0C16T6 is perfect for industries like oil and gas, water and wastewater, mining, and heavy manufacturing, where reliability and energy savings are paramount.
Key Features:
Low Harmonic Technology: The ATV9B0C16T6 features integrated low harmonic technology, which minimizes the total harmonic distortion (THD) to ensure compliance with stringent industry standards. This technology not only enhances power quality but also extends the life of electrical equipment, reducing operational costs and maintenance.
Regenerative Capabilities: Equipped with regenerative braking, this drive can recover and feed energy back into the power grid, significantly lowering energy consumption and operational costs. This feature is especially beneficial in applications with frequent braking cycles, such as cranes, hoists, and conveyors.
High Performance: With a power rating of 160 kW, the ATV9B0C16T6 delivers precise motor control and optimized performance for a wide range of heavy-duty applications. Its advanced motor control algorithms ensure smooth operation, even under the most challenging conditions, providing consistent and reliable performance.
Modular Design: The ATV900 series is known for its modular architecture, allowing for flexible installation and easy integration into existing systems. The modularity also facilitates maintenance and upgrades, ensuring minimal downtime and maximized productivity.
Advanced Connectivity: The ATV9B0C16T6 is equipped with cutting-edge communication protocols, including Ethernet, Modbus, and CANopen, providing seamless integration with industrial networks. This connectivity ensures real-time data exchange, enabling advanced process control and monitoring.
Enhanced Safety: Safety is a priority with the ATV9B0C16T6, which includes integrated safety functions such as Safe Torque Off (STO) and Safe Stop 1 (SS1). These features ensure that the drive meets the highest safety standards, protecting both equipment and personnel.
Energy Efficiency: Designed with energy efficiency in mind, the ATV9B0C16T6 supports the reduction of carbon footprints in industrial processes. Its energy-saving features contribute to significant cost savings over the lifecycle of the equipment.
Applications: The Schneider ATV9B0C16T6 Variable Speed Drive is ideal for a broad range of industrial applications where high performance, energy efficiency, and robust motor control are critical. It is particularly well-suited for:
- Pumping Systems: Optimizes energy usage and ensures smooth operation in water treatment and distribution systems.
- Material Handling: Provides precise control for conveyors, cranes, and hoists, enhancing safety and efficiency.
- HVAC Systems: Delivers energy-efficient solutions for large heating, ventilation, and air conditioning systems.
- Heavy-Duty Manufacturing: Supports complex machinery and processes with high reliability and minimal downtime.
Technical Specifications:
- Power Rating: 160 kW
- Input Voltage: 380-480 V
- Motor Control Type: Variable speed drive with regenerative braking
- Communication Protocols: Ethernet, Modbus, CANopen
- Harmonic Mitigation: Integrated low harmonic technology
- Safety Functions: Safe Torque Off (STO), Safe Stop 1 (SS1)
- Environmental Ratings: IP20 (standard), optional IP54 for harsh environments
- Cooling Method: Forced air cooling
Conclusion: The Schneider ATV9B0C16T6 Variable Speed Drive from the Altivar Process ATV900 series is a cutting-edge solution for industries seeking to optimize performance, enhance energy efficiency, and maintain stringent safety standards. Its advanced features, combined with Schneider Electric’s commitment to quality and innovation, make the ATV9B0C16T6 an indispensable component in modern industrial processes. Whether you are looking to reduce energy costs, improve process control, or ensure compliance with environmental regulations, the ATV9B0C16T6 offers the reliability and performance your operation demands.
Keywords: Schneider ATV9B0C16T6, Altivar Process ATV900, Low Harmonic Drive, Regenerative Drive, Variable Speed Drive, Industrial Automation, Energy Efficiency, Motor Control, Schneider Electric.
range of product |
Altivar Process ATV900
|
|
---|---|---|
product or component type |
Variable speed drive
|
|
device short name |
ATV9B0
|
|
variant |
Modular version
|
|
product destination |
Synchronous motors
Asynchronous motors |
|
mounting mode |
Cabinet mount
|
|
kit composition |
Mechanical mounting kits
Power connection Set of fuses 1 control unit 1 power module 200 kW |
|
EMC filter |
Integrated conforming to EN/IEC 61800-3 category C3 with <= 300
m motor cable maxi
|
|
IP degree of protection |
IP00 conforming to IEC 61800-5-1 for IP21 or IP54 cabinet
integration
IP00 conforming to IEC 60529 for IP21 or IP54 cabinet integration |
|
degree of protection |
UL type 1 UL 61800-5-1 cabinet integration
UL type 12 UL 61800-5-1 cabinet integration |
|
type of cooling |
Forced convection
|
|
supply frequency |
50...60 Hz +/- 5 %
|
|
network number of phases |
3 phases
|
|
[Us] rated supply voltage |
600 V - 10...15 %
|
|
motor power hp |
175 hp at 600 V (normal duty)
150 hp at 600 V (heavy duty) 175 hp at 600 V (normal duty) regenerative mode 150 hp at 600 V (heavy duty) regenerative mode |
|
line current |
121 A at 600 V (heavy duty)
142 A at 600 V (normal duty) 113 A at 600 V (normal duty) regenerative mode 96 A at 600 V (heavy duty) regenerative mode |
|
prospective line Isc |
50 kA
|
|
apparent power |
147 kVA at 600 V (normal duty)
126 kVA at 600 V (heavy duty) 117 kVA at 600 V (normal duty) regenerative mode 100 kVA at 600 V (heavy duty) regenerative mode |
|
continuous output current |
145 A at 2.5 kHz (heavy duty)
175 A at 2.5 kHz (normal duty) 175 A at 2.5 kHz (normal duty) regenerative mode 145 A at 2.5 kHz (heavy duty) regenerative mode |
|
maximum transient current |
217.5 A during 60 s (heavy duty)
210 A during 60 s (normal duty) 210 A during 60 s regenerative mode (normal duty) 217.5 A during 60 s regenerative mode (heavy duty) |
|
speed drive output frequency |
0.1...599 Hz
|
|
nominal switching frequency |
2.5 kHz
|
|
switching frequency |
2...4.9 kHz adjustable with derating factor
|
|
safety function |
STO (safe torque off) SIL 3
|
|
communication port protocol |
Modbus TCP
Modbus serial Ethernet/IP |
|
option module |
Slot A : communication module for Profibus DP V1
Slot A : communication module for Profinet Slot A : communication module for DeviceNet Slot A : communication module for CANopen daisy chain RJ45 Slot A : communication module for CANopen SUB-D 9 Slot A : communication module for CANopen screw terminals Slot A : communication module for EtherCAT Slot A/slot B/slot C : digital and analog I/O extension module Slot A/slot B/slot C : output relay extension module Slot B : analog encoder interface module Slot B : resolver encoder interface module Slot B : digital encoder interface module for 5/12 V |
motor slip compensation |
Automatic whatever the load
Can be suppressed Not available in permanent magnet motor law Adjustable |
|
---|---|---|
acceleration and deceleration ramps |
Linear adjustable separately from 0.01...9999 s
|
|
protection type |
Safe torque off motor
Motor phase break motor Safe torque off drive Overheating drive Short-circuit protection drive Motor phase break drive Overspeed drive Break on the control circuit drive Overvoltages on the DC bus drive Overload of output voltage drive Line supply overvoltage drive Line supply phase loss drive Line supply undervoltage drive Overcurrent between output phases and earth drive Thermal protection motor Thermal protection drive |
|
frequency resolution |
0.012/50 Hz analog input
0.1 Hz display unit |
|
electrical connection |
Removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 control
Screw terminal line side M10 x 2 bars motor |
|
connector type |
2 RJ45 for Ethernet IP/Modbus TCP on terminal
1 RJ45 for Modbus serial on terminal |
|
physical interface |
2-wire RS 485 for Modbus serial
|
|
transmission frame |
RTU for Modbus serial
|
|
transmission rate |
10/100 Mbit/s for Ethernet IP/Modbus TCP
4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial |
|
data format |
8 bits, configurable odd, even or no parity for Modbus serial
|
|
type of polarization |
No impedance for Modbus serial
|
|
number of addresses |
For Modbus serial
|
|
method of access |
Slave for Modbus TCP
|
|
analogue input type |
Software-configurable voltage AI1, AI3 0...10 V DC 30 kOhm 12
bits
Software-configurable current AI1, AI3 0...20 mA/4...20 mA 250 Ohm 12 bits Software-configurable voltage AI2 +/- 10 V DC 30 kOhm 12 bits Software-configurable voltage AI2 0...10 V DC 30 kOhm 12 bits |
THDI |
<= 5 % full load conforming to IEEE 519
|
|
---|---|---|
electromagnetic compatibility |
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to
IEC 61000-4-5
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
|
pollution degree |
2 EN/IEC 61800-5-1
|
|
vibration resistance |
1.5 mm peak to peak 2...13 Hz IEC 60068-2-6
0.5 gn 13...200 Hz IEC 60068-2-6 |
|
shock resistance |
4 gn 11 ms IEC 60068-2-27
|
|
relative humidity |
5...95 % without condensation conforming to IEC 60068-2-3
|
|
ambient air temperature for operation |
40...50 °C with derating factor
-5...40 °C without |
|
ambient air temperature for storage |
-40...70 °C
|
|
operating altitude |
<= 2000 m with current derating above 1000m
|
|
environmental characteristic |
Chemical pollution resistance class 3C3 EN/IEC 60721-3-3
Dust pollution resistance class 3S3 EN/IEC 60721-3-3 |
|
standards |
EN/IEC 61800-3
EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1 |
|
product certifications |
CUL
TÜV UL REACH |
|
marking |
CE
|