Elevate your industrial processes to unprecedented levels of efficiency with the Schneider ATV9B0C31N6 Variable Speed Drive from the renowned Altivar Process Modular ATV900 series. Engineered for precision and performance, this Low Harmonic/Regen Drive is a game-changer in the realm of variable speed control.
Key Features:
Low Harmonic Distortion: The ATV9B0C31N6 is designed to minimize harmonic distortion, ensuring a cleaner power supply and reducing the risk of electrical issues. This translates to enhanced reliability and prolonged equipment life.
Regenerative Capability: Featuring advanced regenerative technology, this drive is capable of converting excess energy back into the power grid. This not only optimizes energy usage but also contributes to a greener and more sustainable operation.
Altivar Process Modular Design: The Altivar Process Modular architecture ensures adaptability to diverse industrial environments. With modular components, the ATV900 series allows for scalability and flexibility, accommodating the evolving needs of your application.
Precise Speed Control: Achieve unparalleled control over motor speed with the ATV9B0C31N6. Whether for constant torque or variable torque applications, this drive provides precise speed regulation, optimizing performance across a wide range of industrial processes.
Comprehensive Connectivity: Seamlessly integrate the ATV9B0C31N6 into your existing automation system with its extensive connectivity options. With compatibility across various communication protocols, including Modbus, Ethernet, and more, this drive ensures easy interoperability.
User-Friendly Interface: The intuitive user interface simplifies configuration and monitoring. A high-resolution display provides real-time data on key performance metrics, enabling operators to make informed decisions and adjustments on the fly.
Robust Construction: Built to withstand demanding industrial environments, the ATV9B0C31N6 boasts a robust and durable design. Its high-quality components ensure reliable operation even in challenging conditions.
Applications:
Industrial Automation: Perfect for applications requiring precise speed control and high efficiency, such as conveyors, pumps, and fans.
Water and Wastewater Treatment: Ideal for optimizing the performance of water and wastewater treatment processes with its low harmonic distortion and regenerative capabilities.
Oil and Gas Industry: Suited for variable speed applications in the oil and gas sector, ensuring efficient and reliable operation.
Elevate your industrial processes with the Schneider ATV9B0C31N6 Variable Speed Drive. Unleash the power of precision, reliability, and sustainability in one advanced package.
Invest in the future of industrial automation. Choose Schneider – where innovation meets performance.
Note: Ensure professional installation and configuration by qualified technicians for optimal performance.
range of product |
Altivar Process ATV900
|
|
---|---|---|
product or component type |
Variable speed drive
|
|
device short name |
ATV9B0
|
|
variant |
Modular version
|
|
product destination |
Synchronous motors
Asynchronous motors |
|
mounting mode |
Cabinet mount
|
|
kit composition |
Mechanical mounting kits
Power connection Set of fuses 1 control unit 1 front cover 2 power module 200 kW |
|
EMC filter |
Integrated conforming to EN/IEC 61800-3 category C3 with <= 300
m motor cable maxi
|
|
IP degree of protection |
IP00 conforming to IEC 61800-5-1 for IP21 or IP54 cabinet
integration
IP00 conforming to IEC 60529 for IP21 or IP54 cabinet integration |
|
degree of protection |
UL type 1 UL 61800-5-1 cabinet integration
UL type 12 UL 61800-5-1 cabinet integration |
|
type of cooling |
Forced convection
|
|
supply frequency |
50...60 Hz +/- 5 %
|
|
network number of phases |
3 phases
|
|
[Us] rated supply voltage |
500 V - 10...15 %
|
|
motor power kW |
220 kW at 500 V (normal duty)
160 kW at 500 V (heavy duty) 220 kW at 500 V (normal duty) regenerative mode 160 kW at 500 V (heavy duty) regenerative mode |
|
line current |
278 A at 500 V (normal duty)
204 A at 500 V (heavy duty) 231 A at 500 V (normal duty) regenerative mode 167 A at 500 V (heavy duty) regenerative mode |
|
prospective line Isc |
50 kA
|
|
apparent power |
241 kVA at 500 V (normal duty)
176 kVA at 500 V (heavy duty) 200 kVA at 500 V (normal duty) regenerative mode 145 kVA at 500 V (heavy duty) regenerative mode |
|
continuous output current |
340 A at 2.5 kHz (normal duty)
275 A at 2.5 kHz (heavy duty) 340 A at 2.5 kHz (normal duty) regenerative mode 275 A at 2.5 kHz (heavy duty) regenerative mode |
|
maximum transient current |
408 A during 60 s (normal duty)
412.5 A during 60 s (heavy duty) 408 A during 60 s regenerative mode (normal duty) 412.5 A during 60 s regenerative mode (heavy duty) |
|
speed drive output frequency |
0.1...599 Hz
|
|
nominal switching frequency |
2.5 kHz
|
|
switching frequency |
2...4.9 kHz adjustable with derating factor
|
|
safety function |
STO (safe torque off) SIL 3
|
|
communication port protocol |
Ethernet/IP
Modbus serial Modbus TCP |
|
option module |
Slot A : communication module for Profibus DP V1
Slot A : communication module for Profinet Slot A : communication module for DeviceNet Slot A : communication module for CANopen daisy chain RJ45 Slot A : communication module for CANopen SUB-D 9 Slot A : communication module for CANopen screw terminals Slot A : communication module for EtherCAT Slot A/slot B/slot C : digital and analog I/O extension module Slot A/slot B/slot C : output relay extension module Slot B : analog encoder interface module Slot B : resolver encoder interface module Slot B : digital encoder interface module for 5/12 V |
motor slip compensation |
Adjustable
Not available in permanent magnet motor law Automatic whatever the load Can be suppressed |
|
---|---|---|
acceleration and deceleration ramps |
Linear adjustable separately from 0.01...9999 s
|
|
protection type |
Safe torque off motor
Motor phase break motor Safe torque off drive Overheating drive Short-circuit protection drive Motor phase break drive Overspeed drive Break on the control circuit drive Overvoltages on the DC bus drive Overload of output voltage drive Line supply overvoltage drive Line supply phase loss drive Line supply undervoltage drive Overcurrent between output phases and earth drive Thermal protection motor Thermal protection drive |
|
frequency resolution |
0.012/50 Hz analog input
0.1 Hz display unit |
|
electrical connection |
Removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 control
Screw terminal line side M10 x 2 bars motor |
|
connector type |
2 RJ45 for Ethernet IP/Modbus TCP on terminal
1 RJ45 for Modbus serial on terminal |
|
physical interface |
2-wire RS 485 for Modbus serial
|
|
transmission frame |
RTU for Modbus serial
|
|
transmission rate |
10/100 Mbit/s for Ethernet IP/Modbus TCP
4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial |
|
data format |
8 bits, configurable odd, even or no parity for Modbus serial
|
|
type of polarization |
No impedance for Modbus serial
|
|
number of addresses |
For Modbus serial
|
|
method of access |
Slave for Modbus TCP
|
|
analogue input type |
Software-configurable voltage AI1, AI3 0...10 V DC 30 kOhm 12
bits
Software-configurable current AI1, AI3 0...20 mA/4...20 mA 250 Ohm 12 bits Software-configurable voltage AI2 +/- 10 V DC 30 kOhm 12 bits Software-configurable voltage AI2 0...10 V DC 30 kOhm 12 bits |
THDI |
<= 5 % full load conforming to IEEE 519
|
|
---|---|---|
electromagnetic compatibility |
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to
IEC 61000-4-5
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
|
pollution degree |
2 EN/IEC 61800-5-1
|
|
vibration resistance |
1.5 mm peak to peak 2...13 Hz IEC 60068-2-6
0.5 gn 13...200 Hz IEC 60068-2-6 |
|
shock resistance |
4 gn 11 ms IEC 60068-2-27
|
|
relative humidity |
5...95 % without condensation conforming to IEC 60068-2-3
|
|
ambient air temperature for operation |
40...50 °C with derating factor
-5...40 °C without |
|
ambient air temperature for storage |
-40...70 °C
|
|
operating altitude |
<= 2000 m with current derating above 1000m
|
|
environmental characteristic |
Chemical pollution resistance class 3C3 EN/IEC 60721-3-3
Dust pollution resistance class 3S3 EN/IEC 60721-3-3 |
|
standards |
EN/IEC 61800-3
EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 |
|
product certifications |
UL
TÜV REACH CUL |
|
marking |
CE
|