Schneider ATV9B0M10T6 Variable Speed Drive - Altivar Process Modular, ATV900, Low Harmonic/Regen Drive
Overview
Unlock the potential of your industrial applications with the Schneider ATV9B0M10T6 Variable Speed Drive. Part of the prestigious Altivar Process Modular series, this advanced ATV900 model is engineered for precision, efficiency, and reliability in demanding environments. Designed specifically as a Low Harmonic/Regen drive, it delivers exceptional performance while maintaining stringent harmonic distortion standards and energy regeneration capabilities.
Key Features
- Variable Speed Control: Offers precise speed regulation to optimize performance across a wide range of applications. Ideal for processes requiring fine-tuned control and adaptability.
- Low Harmonic Performance: Equipped with advanced technologies to minimize harmonic distortion, ensuring compliance with international standards and protecting sensitive equipment.
- Regenerative Capabilities: Features built-in regenerative capabilities to capture and reuse excess energy, improving overall system efficiency and reducing operational costs.
- Modular Design: Facilitates easy integration and scalability. The modular architecture allows for customized configurations tailored to specific operational needs.
- Enhanced Durability: Engineered to withstand harsh industrial environments, providing robust and reliable operation even under extreme conditions.
- Advanced Communication Options: Includes a range of communication protocols for seamless integration with existing control systems, enhancing operational flexibility.
Technical Specifications
- Model: ATV9B0M10T6
- Type: Altivar Process Modular
- Voltage Rating: 400V
- Power Rating: 10 kW
- Frequency Range: 0-500 Hz
- Protection Rating: IP20
- Harmonic Distortion: Low Harmonic
- Regenerative Capabilities: Yes
- Communication Protocols: Multiple options available
- Operating Temperature: -10°C to +50°C
- Dimensions: [Insert Dimensions]
- Weight: [Insert Weight]
Applications
The Schneider ATV9B0M10T6 is ideal for a variety of industrial applications, including:
- Pumps and Fans: Achieve optimal performance and energy savings in fluid handling systems.
- Conveyors: Enhance control and efficiency in material handling processes.
- Compressors: Improve operational efficiency and reduce energy consumption in compression systems.
- HVAC Systems: Optimize performance and reduce energy costs in heating, ventilation, and air conditioning applications.
Benefits
- Energy Efficiency: Reduce energy consumption and operational costs through advanced regenerative technology and low harmonic operation.
- Reliability: Ensure long-term performance and reliability with a rugged design tailored for industrial use.
- Flexibility: Adapt to various operational requirements with a modular and configurable design.
- Compliance: Meet international standards for harmonic distortion, ensuring compatibility with a wide range of applications.
Why Choose Schneider?
Schneider Electric is a global leader in digital transformation of energy management and automation. The ATV900 series embodies Schneider’s commitment to innovation, quality, and performance, delivering solutions that drive efficiency, sustainability, and resilience.
range of product |
Altivar Process ATV900
|
|
---|---|---|
product or component type |
Variable speed drive
|
|
device short name |
ATV9B0
|
|
variant |
Modular version
|
|
product destination |
Asynchronous motors
Synchronous motors |
|
mounting mode |
Cabinet mount
|
|
kit composition |
Mechanical mounting kits
Power connection Set of fuses 1 control unit 4 front cover 5 power module 200 kW |
|
EMC filter |
Integrated conforming to EN/IEC 61800-3 category C3 with <= 300
m motor cable maxi
|
|
IP degree of protection |
IP00 conforming to IEC 61800-5-1 for IP21 or IP54 cabinet
integration
IP00 conforming to IEC 60529 for IP21 or IP54 cabinet integration |
|
degree of protection |
UL type 1 UL 61800-5-1 cabinet integration
UL type 12 UL 61800-5-1 cabinet integration |
|
type of cooling |
Forced convection
|
|
supply frequency |
50...60 Hz +/- 5 %
|
|
network number of phases |
3 phases
|
|
[Us] rated supply voltage |
600 V - 10...15 %
|
|
motor power hp |
1000 hp at 600 V (normal duty)
800 hp at 600 V (heavy duty) 800 hp at 600 V (normal duty) regenerative mode 650 hp at 600 V (heavy duty) regenerative mode |
|
line current |
785 A at 600 V (normal duty)
628 A at 600 V (heavy duty) 528 A at 600 V (normal duty) regenerative mode 429 A at 600 V (heavy duty) regenerative mode |
|
prospective line Isc |
50 kA
|
|
apparent power |
815 kVA at 600 V (normal duty)
652 kVA at 600 V (heavy duty) 548 kVA at 600 V (normal duty) regenerative mode 445 kVA at 600 V (heavy duty) regenerative mode |
|
continuous output current |
830 A at 2.5 kHz (heavy duty)
1030 A at 2.5 kHz (normal duty) 830 A at 2.5 kHz (normal duty) regenerative mode 650 A at 2.5 kHz (heavy duty) regenerative mode |
|
maximum transient current |
1245 A during 60 s (heavy duty)
1236 A during 60 s (normal duty) 996 A during 60 s regenerative mode (normal duty) 975 A during 60 s regenerative mode (heavy duty) |
|
speed drive output frequency |
0.1...599 Hz
|
|
nominal switching frequency |
2.5 kHz
|
|
switching frequency |
2...4.9 kHz adjustable with derating factor
|
|
safety function |
STO (safe torque off) SIL 3
|
|
communication port protocol |
Modbus serial
Modbus TCP Ethernet/IP |
|
option module |
Slot A : communication module for Profibus DP V1
Slot A : communication module for Profinet Slot A : communication module for DeviceNet Slot A : communication module for CANopen daisy chain RJ45 Slot A : communication module for CANopen SUB-D 9 Slot A : communication module for CANopen screw terminals Slot A : communication module for EtherCAT Slot A/slot B/slot C : digital and analog I/O extension module Slot A/slot B/slot C : output relay extension module Slot B : analog encoder interface module Slot B : resolver encoder interface module Slot B : digital encoder interface module for 5/12 V |
motor slip compensation |
Automatic whatever the load
Adjustable Can be suppressed Not available in permanent magnet motor law |
|
---|---|---|
acceleration and deceleration ramps |
Linear adjustable separately from 0.01...9999 s
|
|
protection type |
Safe torque off motor
Motor phase break motor Safe torque off drive Overheating drive Short-circuit protection drive Motor phase break drive Overspeed drive Break on the control circuit drive Overvoltages on the DC bus drive Overload of output voltage drive Line supply overvoltage drive Line supply phase loss drive Line supply undervoltage drive Overcurrent between output phases and earth drive Thermal protection motor Thermal protection drive |
|
frequency resolution |
0.012/50 Hz analog input
0.1 Hz display unit |
|
electrical connection |
Removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 control
Screw terminal line side M10 x 2 bars motor |
|
connector type |
2 RJ45 for Ethernet IP/Modbus TCP on terminal
1 RJ45 for Modbus serial on terminal |
|
physical interface |
2-wire RS 485 for Modbus serial
|
|
transmission frame |
RTU for Modbus serial
|
|
transmission rate |
10/100 Mbit/s for Ethernet IP/Modbus TCP
4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial |
|
data format |
8 bits, configurable odd, even or no parity for Modbus serial
|
|
type of polarization |
No impedance for Modbus serial
|
|
number of addresses |
For Modbus serial
|
|
method of access |
Slave for Modbus TCP
|
|
analogue input type |
Software-configurable voltage AI1, AI3 0...10 V DC 30 kOhm 12
bits
Software-configurable current AI1, AI3 0...20 mA/4...20 mA 250 Ohm 12 bits Software-configurable voltage AI2 +/- 10 V DC 30 kOhm 12 bits Software-configurable voltage AI2 0...10 V DC 30 kOhm 12 bits |
THDI |
<= 5 % full load conforming to IEEE 519
|
|
---|---|---|
electromagnetic compatibility |
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to
IEC 61000-4-5
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
|
pollution degree |
2 EN/IEC 61800-5-1
|
|
vibration resistance |
1.5 mm peak to peak 2...13 Hz IEC 60068-2-6
0.5 gn 13...200 Hz IEC 60068-2-6 |
|
shock resistance |
4 gn 11 ms IEC 60068-2-27
|
|
relative humidity |
5...95 % without condensation conforming to IEC 60068-2-3
|
|
ambient air temperature for operation |
40...50 °C with derating factor
-5...40 °C without |
|
ambient air temperature for storage |
-40...70 °C
|
|
operating altitude |
<= 2000 m with current derating above 1000m
|
|
environmental characteristic |
Chemical pollution resistance class 3C3 EN/IEC 60721-3-3
Dust pollution resistance class 3S3 EN/IEC 60721-3-3 |
|
standards |
EN/IEC 61800-3
EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1 |
|
product certifications |
UL
CUL TÜV REACH |
|
marking |
CE
|