Enhance the operational capacity of your control system with the Schneider TM3DI8A Module TM3. This cutting-edge module offers a seamless integration solution, featuring 8 inputs designed to accommodate 120V AC, delivering unparalleled versatility and performance in industrial automation applications.
Key Features:
- Enhanced Input Capacity: The TM3DI8A Module TM3 extends the input capabilities of your control systems, offering 8 high-quality inputs compatible with 120V AC, ensuring efficient and precise data acquisition.
- Versatile Compatibility: Engineered for seamless integration with Schneider control systems, this module provides a plug-and-play solution, streamlining the incorporation process into your existing setup.
- Reliable Performance: Built with robust components and adhering to stringent quality standards, this module ensures consistent and reliable performance in demanding industrial environments.
- Effortless Installation: Designed with user convenience in mind, the TM3DI8A Module TM3 facilitates quick and hassle-free installation, minimizing downtime and optimizing operational efficiency.
Applications:
- Industrial Automation: Ideal for diverse industrial automation applications, including manufacturing, process control, and machinery operation, offering precise and reliable input data acquisition.
- Control Systems Enhancement: Seamlessly integrates into existing control systems, enhancing their input capacity and enabling smoother and more efficient operations.
Technical Specifications:
- Input Type: 8 inputs compatible with 120V AC.
- Compatibility: Compatible with Schneider control systems.
- Dimensions: [Include dimensions if available]
- Operating Environment: Designed to operate reliably in varied industrial environments.
Benefit from the unparalleled input expansion capabilities of the Schneider TM3DI8A Module TM3. Maximize operational efficiency, streamline processes, and elevate your industrial automation setup with this high-performance module.
Ensure precision, reliability, and seamless integration in your control systems with the Schneider TM3DI8A Module TM3. Contact us now to discover how this cutting-edge module can revolutionize your industrial automation setup.
range of product |
Modicon TM3
|
|
---|---|---|
product or component type |
Discrete input module
|
|
range compatibility |
Modicon M251
Modicon M241 Modicon M221 |
|
discrete input number |
8 input conforming to IEC 61131-2 Type 1
|
|
discrete input voltage |
120 V
|
|
discrete input current |
7.5 mA for input
|
discrete I/O number |
8
|
|
---|---|---|
current consumption |
0 mA at 24 V DC via bus connector at state on
0 mA at 24 V DC via bus connector at state off 70 mA at 5 V DC via bus connector at state on 25 mA at 5 V DC via bus connector at state off |
|
discrete input voltage type |
AC
|
|
voltage state 1 guaranteed |
79...132 V for input
|
|
current state 1 guaranteed |
2...15 mA for input
|
|
voltage state 0 guaranteed |
0...20 V for input
|
|
current state 0 guaranteed |
<= 15 mA for input
|
|
input impedance |
11 kOhm
|
|
response time |
25 ms for turn-on
30 ms for turn-off |
|
local signalling |
1 LED per channel green for input status
|
|
electrical connection |
Removable screw terminal block pitch 5.08 mm with 11 terminal(s)
of 2.5 mm² connection capacity for inputs
|
|
insulation |
Non-insulated between inputs
1500 V AC between input and internal logic 1500 V AC between input groups |
|
marking |
CE
|
|
mounting support |
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715 Plate or panel with fixing kit |
|
height |
90 mm
|
|
depth |
84.6 mm
|
|
width |
27.4 mm
|
standards |
EN/IEC 61131-2
EN/IEC 61010-2-201 |
|
---|---|---|
product certifications |
C-Tick
cULus |
|
resistance to electrostatic discharge |
4 kV (on contact) conforming to EN/IEC 61000-4-2
8 kV (in air) conforming to EN/IEC 61000-4-2 |
|
resistance to electromagnetic fields |
10 V/m at 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m at 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 1 V/m at 2 GHz...3 GHz conforming to EN/IEC 61000-4-3 |
|
resistance to magnetic fields |
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
|
|
resistance to fast transients |
1 kV for I/O conforming to EN/IEC 61000-4-4
|
|
surge withstand |
2 kV for I/O (AC) in common mode conforming to EN/IEC 61000-4-5
|
|
resistance to conducted disturbances |
10 Vrms at 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 Vrms at spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
|
electromagnetic emission |
Radiated emissions, test level: 40 dBμV/m QP with class A,
condition of test: 10 m (radio frequency: 30...230 MHz)
conforming to EN/IEC 55011
Radiated emissions, test level: 47 dBμV/m QP with class A, condition of test: 10 m (radio frequency: 230...1000 MHz) conforming to EN/IEC 55011 |
|
ambient air temperature for operation |
-10...55 °C for horizontal installation
-10...35 °C for vertical installation |
|
ambient air temperature for storage |
-25...70 °C
|
|
relative humidity |
10...95 % without condensation in operation
10...95 % without condensation in storage |
|
IP degree of protection |
IP20 with protective cover in place
|
|
pollution degree |
2
|
|
operating altitude |
0...2000 m
|
|
storage altitude |
0...3000 m
|
|
vibration resistance |
3.5 mm (vibration frequency: 5...8.4 Hz) on DIN rail
3 gn (vibration frequency: 8.4...150 Hz) on DIN rail 3.5 mm (vibration frequency: 5...8.4 Hz) on panel 3 gn (vibration frequency: 8.4...150 Hz) on panel |
|
shock resistance |
15 gn (test wave duration:11 ms)
|