Schneider TM3SAF5RG Safety Module for PLC TM2xx – 1 Function, Category 4, Spring Terminals
Overview: The Schneider TM3SAF5RG Safety Module is a high-performance, advanced safety solution designed specifically for use with the Schneider Electric TM2xx PLC series. Engineered to meet stringent safety requirements, this module ensures reliable and efficient safety management in industrial automation systems. It supports a wide range of applications requiring safety functionality and integrates seamlessly into existing control systems, providing robust protection and enhancing operational safety.
Key Features:
Functionality: The TM3SAF5RG offers a single-function safety module designed to implement a Category 4 safety solution, according to the IEC 61508 and ISO 13849 standards. It is ideal for applications requiring high levels of safety integrity and reliability.
Category 4 Safety: Compliant with Category 4 (Cat4) safety standards, the module ensures the highest level of safety performance, providing advanced protection for critical applications. This categorization is essential for safeguarding personnel and equipment in demanding industrial environments.
Spring Terminals: The module features user-friendly spring terminals, which simplify wiring and maintenance. The spring terminal design allows for quick and secure connections, minimizing installation time and reducing the risk of wiring errors.
Compatibility: The TM3SAF5RG is specifically designed for integration with the Schneider TM2xx PLC series, ensuring compatibility and optimal performance within Schneider Electric’s automation ecosystem. This modular approach facilitates streamlined system expansion and integration.
Reliability: Built with Schneider Electric’s renowned quality standards, the TM3SAF5RG is engineered to deliver consistent and dependable performance. Its robust construction and advanced safety features ensure long-term reliability and durability in demanding operational conditions.
Applications: The Schneider TM3SAF5RG Safety Module is suitable for a variety of industrial applications where safety is a critical concern. It is commonly used in machinery and equipment control, conveyor systems, automated production lines, and other environments where safety integrity is paramount.
Technical Specifications:
- Model: TM3SAF5RG
- Function: 1 Function Safety Module
- Safety Category: Category 4 (Cat4)
- Connection Type: Spring Terminals
- Compatibility: Schneider TM2xx PLC Series
- Standards Compliance: IEC 61508, ISO 13849
- Installation: Easy mounting with spring terminals for quick and secure connections
Advantages:
- Enhanced Safety: Meets high safety standards, providing reliable protection and reducing risk in automated systems.
- Ease of Use: Spring terminal connections simplify installation and maintenance.
- Seamless Integration: Designed for compatibility with TM2xx PLCs, ensuring smooth integration into existing systems.
Conclusion: The Schneider TM3SAF5RG Safety Module is a premium solution for implementing high-level safety features within your automation system. Its adherence to Category 4 safety standards, coupled with user-friendly spring terminals and compatibility with the TM2xx PLC series, makes it an essential component for ensuring operational safety and efficiency.
For more information or to purchase the Schneider TM3SAF5RG Safety Module, please visit [Your Website] or contact our sales team.
range of product |
Modicon TM3 Safety
|
|
---|---|---|
product or component type |
Safety module
|
|
device short name |
TM3SAF
|
|
safety module application |
For emergency stop and switch monitoring
|
|
function of module |
Emergency stop monitoring 1-channel wiring
Emergency stop monitoring 2-channel wiring Monitoring of a movable guard with 2 switches and automatic start |
|
safety level |
Can reach PL e/category 4 EN/ISO 13849-1:2008
Can reach PL e/category 4 EN/ISO 13849-2:2012 Can reach SILCL 3 EN/IEC 62061:2005 Can reach SIL 3 EN/IEC 61508:2010 |
safety reliability data |
DC = 95 % EN/ISO 13849-1
PFHd = 5E-9 1/h IEC 61508-1 1 operation/hour DC-13 24 V DC 4 A PFHd = 30E-9 1/h IEC 61508-1 60 operations/hour DC-13 24 V DC 1 A MTTFd = 500 years EN/ISO 13849-1 1 operation/hour DC-13 24 V DC 4 A MTTFd = 85 years EN/ISO 13849-1 60 operations/hour DC-13 24 V DC 1 A SFF = 95 % IEC 61508-1 HFT = 1 IEC 61508-1 Type = A IEC 61508-1 |
|
---|---|---|
synchronisation time between inputs |
Unlimited
|
|
connections - terminals |
Captive spring terminals, removable terminal block 1 x 0.2...1 x
2.5 mm² flexible without cable end 13-14, 23-24, 33-34
Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals Captive spring terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals Captive spring terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals |
|
output type |
Relay instantaneous opening 3 NO potential free
|
|
number of safety circuits |
3 NO (relay instantaneous opening)
|
|
maximum switching voltage |
230 V utilisation category AC-15 at 50 Hz (relay instantaneous
opening)
24 V utilisation category DC-13 (relay instantaneous opening) |
|
[Us] rated supply voltage |
24 V DC - 15...20 %
|
|
power consumption in W |
0.2 W 5 V DC
3.6 W 24 V DC |
|
input protection type |
Internal, electronic
|
|
[Uc] control circuit voltage |
24 V DC
|
|
cable distance between devices |
30 m
|
|
breaking capacity |
360 VA holding AC-15 B300 relay output
3600 VA inrush AC-15 B300 relay output |
|
breaking capacity |
4 A 24 V 50 ms DC-13 relay output
|
|
output thermal current |
6 A per relay relay output
|
|
[Ith] conventional free air thermal current |
18 A
|
|
associated fuse rating |
4 A gG or gL relay output EN/IEC 60947-5-1
6 A fast blow relay output EN/IEC 60947-5-1 |
|
minimum output current |
10 mA relay output
|
|
output voltage |
10 V relay output
|
|
response time on input open |
<= 40 ms
|
|
[Ui] rated insulation voltage |
300 V 2 IEC 60647-5-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV III IEC 60647-5-1
|
|
current consumption |
100 mA 24 V DC external supply
|
|
local signalling |
8 LEDs green/red user
|
|
electrical connection |
Spring terminal
|
|
standards |
EN/ISO 13849-1:2008
EN/ISO 13849-2:2012 EN/IEC 62061:2005 EN/IEC 61508:2010 EN/IEC 60947-5-1:2010 EN/IEC 61131-2:2007 EN/IEC 60204-1:2005 EN/IEC 60204-1:2009/A1 IEC 61010-1:2010 EN 50581:2012 |
|
product certifications |
EAC
RCM ANSI Haz Loc Class 1 Division 2 (pending) UL 61010-2-201 CSA 61010-2-201 (pending) CSA Haz Loc Class 1 Division 2 (pending) TÜV |
|
marking |
UL
REACH CE TÜV EFUP 10 CSA RCM EAC |
|
electromagnetic compatibility |
Electrostatic discharge immunity test 8 kV air discharge
conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test 6 kV contact discharge conforming to EN/IEC 61000-4-2 Susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz conforming to EN/IEC 61000-4-3 Susceptibility to electromagnetic fields 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 Susceptibility to electromagnetic fields 1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3 Magnetic field at power frequency 30 A/m 50...60 Hz conforming to EN/IEC 61000-4-8 Electrical fast transient/burst immunity test 3 kV power lines (DC) conforming to EN/IEC 61000-4-4 Electrical fast transient/burst immunity test 2 kV I/O conforming to EN/IEC 61000-4-4 1.2/50 µs shock waves immunity test 1 kV power lines (DC) conforming to EN/IEC 61000-4-5 Conducted RF disturbances 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 Radiated emission 40 dBµV/m class A 24 V conforming to EN 55011 Radiated emission 47 dBµV/m class A 24 V conforming to EN 55011 |
|
mounting support |
Wall mount using attached fasteners
Rail top hat type TH35-7.5 IEC 60715 Rail top hat type TH35-15 IEC 60715 |
|
height |
94 mm
|
|
depth |
73 mm
|
|
width |
43.7 mm
|
|
product weight |
0.19 kg
|
standards |
EN/IEC 60947-5-1
EN 1088/ISO 14119 EN/IEC 60947-1 EN/ISO 13850 EN 60204-1 |
|
---|---|---|
resistance to electrostatic discharge |
6 kV on contact EN/IEC 61000-4-2
8 kV in air EN/IEC 61000-4-2 |
|
resistance to electromagnetic fields |
10 V/m 80 MHz...1 GHz EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz EN/IEC 61000-4-3 1 V/m 2 GHz...3 GHz EN/IEC 61000-4-3 |
|
resistance to magnetic fields |
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
|
|
resistance to fast transients |
3 kV power lines (DC) EN/IEC 61000-4-4 DC
2 kV I/O lines EN/IEC 61000-4-4 |
|
surge withstand |
1 kV power lines (DC) differential mode EN/IEC 61000-4-5 DC
1 kV power lines (DC) common mode EN/IEC 61000-4-5 DC |
|
resistance to conducted disturbances |
10 V 0.15...80 MHz EN/IEC 61000-4-6
|
|
electromagnetic emission |
Radiated emissions 50 dBµV/m class A 24 V DC 30...230 Hz IEC
61131-3
Radiated emissions 57 dBµV/m class A 24 V DC 230...1000 Hz IEC 61131-3 |
|
ambient air temperature for operation |
-10...55 °C horizontal installation
|
|
ambient air temperature for storage |
-25...70 °C
|
|
relative humidity |
10...95 % without condensation in operation
10...95 % without condensation in storage |
|
IP degree of protection |
IP20 EN/IEC 60529 terminals
|
|
pollution degree |
2
|
|
operating altitude |
0...2000 m
|
|
storage altitude |
0...3000 m
|
|
vibration resistance |
+/- 3.5 mm 5...150 Hz IEC 60068-2-6
|
|
shock resistance |
15 gn 11 ms IEC 60068-2-27
|
|
mechanical robustness |
Bumps 6 ms 300 shocks 25 gn IEC 60068-2-27
|
Schneider TM3SAF5RG Safety Module for PLC TM2xx – 1 Function, Category 4, Spring Terminals
- Brand: Schneider
- Product Code: TM3SAF5RG
- Availability: 1000
Tags: Schneider TM3SAF5RG, Safety Module, PLC TM2xx, Category 4, Spring Terminals, Industrial Safety, Automation, Schneider Electric, High-Level Safety, Safety Solutions