Schneider TM3SAFL5R Safety Module for PLC TM2xx
Overview:
The Schneider TM3SAFL5R Safety Module is a high-performance safety solution designed for use with the Schneider TM2xx PLC series. This advanced safety module is engineered to provide reliable and robust safety functions to ensure the secure operation of automated machinery and processes. Adhering to the highest standards of safety and compliance, the TM3SAFL5R is ideal for applications requiring Category 3 safety functionality and precision control.
Key Features:
Functions: The TM3SAFL5R offers dual safety functions, providing enhanced flexibility and control in various safety applications. Its versatile functionality supports a wide range of safety requirements, making it a valuable component in complex safety systems.
Category 3 Compliance: This safety module conforms to Category 3 safety standards, ensuring high levels of protection and reliability. It is designed to meet rigorous safety requirements, reducing risks and enhancing overall system integrity.
Screw Terminals: Equipped with screw terminals for secure and reliable connections, the TM3SAFL5R facilitates straightforward wiring and installation. The screw terminal design ensures stable connections and minimizes the risk of loose or faulty wiring.
Compatibility: Specifically designed for integration with the Schneider TM2xx PLC series, the TM3SAFL5R seamlessly integrates into existing automation systems, providing an effective safety solution with minimal setup and configuration.
Robust Construction: Built to withstand demanding industrial environments, the TM3SAFL5R features a durable construction that ensures long-term performance and reliability. Its robust design is ideal for use in harsh conditions, contributing to the module's longevity and operational stability.
Applications:
The Schneider TM3SAFL5R Safety Module is suitable for a range of applications, including:
- Industrial machinery and equipment
- Automated production lines
- Safety-critical systems requiring Category 3 compliance
- Applications needing reliable and flexible safety functions
Technical Specifications:
- Functionality: 2 safety functions
- Safety Category: Category 3
- Terminal Type: Screw terminals
- Compatibility: Schneider TM2xx PLC series
Benefits:
- Enhanced Safety: Provides high levels of safety compliance and protection for automated systems.
- Flexible Integration: Easily integrates with Schneider TM2xx PLCs, offering versatile safety solutions.
- Reliable Performance: Durable construction and secure screw terminals ensure consistent and reliable operation.
Conclusion:
The Schneider TM3SAFL5R Safety Module is an essential component for achieving high safety standards in automated systems. Its dual-function capability, Category 3 compliance, and secure screw terminals make it a reliable choice for enhancing safety and efficiency in industrial applications. Invest in the Schneider TM3SAFL5R for a robust, flexible, and reliable safety solution tailored to meet the demands of modern automation systems.
range of product |
Modicon TM3 Safety
|
|
---|---|---|
product or component type |
Safety module
|
|
device short name |
TM3SAFL
|
|
safety module application |
For emergency stop, switch and safety light curtain monitoring
|
|
function of module |
Emergency stop monitoring 2-channel wiring
Monitoring of a movable guard Multiple emergency stop monitoring 2-channel wiring Monitoring of electro-sensitive protection equipment (ESPE) PNP/PNP Proximity sensor monitoring PNP/PNP Monitoring of a movable guard with 2 switches and automatic start |
|
safety level |
Can reach PL d/category 3 EN/ISO 13849-1:2008
Can reach PL d/category 3 EN/ISO 13849-2:2012 Can reach SILCL 2 EN/IEC 62061:2005 Can reach SIL 2 EN/IEC 61508:2010 |
safety reliability data |
DC = 95 % EN/ISO 13849-1
PFHd = 5E-9 1/h IEC 61508-1 1 operation/hour DC-13 24 V DC 4 A PFHd = 30E-9 1/h IEC 61508-1 60 operations/hour DC-13 24 V DC 1 A MTTFd = 500 years EN/ISO 13849-1 1 operation/hour DC-13 24 V DC 4 A MTTFd = 85 years EN/ISO 13849-1 60 operations/hour DC-13 24 V DC 1 A SFF = 95 % IEC 61508-1 HFT = 1 IEC 61508-1 Type = A IEC 61508-1 |
|
---|---|---|
synchronisation time between inputs |
Unlimited
|
|
connections - terminals |
Captive screw clamp terminals, removable terminal block 1 x
0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34
Captive screw clamp terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.2...2 x 1.5 mm² flexible without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.2...2 x 1.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34 Captive screw clamp terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals Captive screw clamp terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals Captive screw clamp terminals, removable terminal block 2 x 0.14...2 x 0.5 mm² flexible without cable end other terminals Captive screw clamp terminals, removable terminal block 2 x 0.14...2 x 0.75 mm² solid without cable end other terminals Captive screw clamp terminals, removable terminal block 2 x 0.25...2 x 0.34 mm² flexible with cable end, without bezel other terminals Captive screw clamp terminals, removable terminal block 2 x 0.5 mm² flexible with cable end, with double bezel other terminals |
|
output type |
Relay instantaneous opening 3 NO potential free
|
|
number of safety circuits |
3 NO (relay instantaneous opening)
|
|
maximum switching voltage |
230 V utilisation category AC-15 at 50 Hz (relay instantaneous
opening)
24 V utilisation category DC-13 (relay instantaneous opening) |
|
[Us] rated supply voltage |
24 V DC - 15...20 %
|
|
power consumption in W |
0.2 W 5 V DC
3.6 W 24 V DC |
|
input protection type |
Internal, electronic
|
|
[Uc] control circuit voltage |
24 V DC
|
|
cable distance between devices |
30 m
|
|
breaking capacity |
360 VA holding AC-15 B300 relay output
3600 VA inrush AC-15 B300 relay output |
|
breaking capacity |
4 A 24 V 50 ms DC-13 relay output
|
|
output thermal current |
6 A per relay relay output
|
|
[Ith] conventional free air thermal current |
18 A
|
|
associated fuse rating |
4 A gG or gL relay output EN/IEC 60947-5-1
6 A fast blow relay output EN/IEC 60947-5-1 |
|
minimum output current |
10 mA relay output
|
|
output voltage |
10 V relay output
|
|
response time on input open |
<= 40 ms
|
|
[Ui] rated insulation voltage |
300 V 2 IEC 60647-5-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV III IEC 60647-5-1
|
|
current consumption |
100 mA 24 V DC external supply
|
|
local signalling |
8 LEDs green/red user
|
|
electrical connection |
Screw terminal
|
|
product compatibility |
Safety light curtains EN/IEC 61496-1 (type 4)
|
|
standards |
EN/ISO 13849-1:2008
EN/ISO 13849-2:2012 EN/IEC 62061:2005 EN/IEC 61508:2010 EN/IEC 60947-5-1:2010 EN/IEC 61131-2:2007 EN/IEC 60204-1:2005 EN/IEC 60204-1:2009/A1 IEC 61010-1:2010 EN 50581:2012 |
|
product certifications |
UL 61010-2-201
TÜV ANSI Haz Loc Class 1 Division 2 (pending) CSA 61010-2-201 (pending) CSA Haz Loc Class 1 Division 2 (pending) RCM EAC |
|
marking |
REACH
EAC TÜV EFUP 10 CE UL RCM CSA |
|
electromagnetic compatibility |
Electrostatic discharge immunity test 8 kV air discharge
conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test 6 kV contact discharge conforming to EN/IEC 61000-4-2 Susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz conforming to EN/IEC 61000-4-3 Susceptibility to electromagnetic fields 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 Susceptibility to electromagnetic fields 1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3 Magnetic field at power frequency 30 A/m 50...60 Hz conforming to EN/IEC 61000-4-8 Electrical fast transient/burst immunity test 3 kV power lines (DC) conforming to EN/IEC 61000-4-4 Electrical fast transient/burst immunity test 2 kV I/O conforming to EN/IEC 61000-4-4 1.2/50 µs shock waves immunity test 1 kV power lines (DC) conforming to EN/IEC 61000-4-5 Conducted RF disturbances 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 Radiated emission 40 dBµV/m class A 24 V conforming to EN 55011 Radiated emission 47 dBµV/m class A 24 V conforming to EN 55011 |
|
mounting support |
Wall mount using attached fasteners
Rail top hat type TH35-7.5 IEC 60715 Rail top hat type TH35-15 IEC 60715 |
|
height |
94 mm
|
|
depth |
73 mm
|
|
width |
43.7 mm
|
|
product weight |
0.19 kg
|
standards |
EN 1088/ISO 14119
EN/ISO 13850 EN/IEC 60947-5-1 EN/IEC 60947-1 EN 60204-1 |
|
---|---|---|
resistance to electrostatic discharge |
6 kV on contact EN/IEC 61000-4-2
8 kV in air EN/IEC 61000-4-2 |
|
resistance to electromagnetic fields |
10 V/m 80 MHz...1 GHz EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz EN/IEC 61000-4-3 1 V/m 2 GHz...3 GHz EN/IEC 61000-4-3 |
|
resistance to magnetic fields |
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
|
|
resistance to fast transients |
3 kV power lines (DC) EN/IEC 61000-4-4 DC
2 kV I/O lines EN/IEC 61000-4-4 |
|
surge withstand |
1 kV power lines (DC) differential mode EN/IEC 61000-4-5 DC
1 kV power lines (DC) common mode EN/IEC 61000-4-5 DC |
|
resistance to conducted disturbances |
10 V 0.15...80 MHz EN/IEC 61000-4-6
|
|
electromagnetic emission |
Radiated emissions 50 dBµV/m class A 24 V DC 30...230 Hz IEC
61131-3
Radiated emissions 57 dBµV/m class A 24 V DC 230...1000 Hz IEC 61131-3 |
|
ambient air temperature for operation |
-10...55 °C horizontal installation
|
|
ambient air temperature for storage |
-25...70 °C
|
|
relative humidity |
10...95 % without condensation in operation
10...95 % without condensation in storage |
|
IP degree of protection |
IP20 EN/IEC 60529 terminals
|
|
pollution degree |
2
|
|
operating altitude |
0...2000 m
|
|
storage altitude |
0...3000 m
|
|
vibration resistance |
+/- 3.5 mm 5...150 Hz IEC 60068-2-6
|
|
shock resistance |
15 gn 11 ms IEC 60068-2-27
|
|
mechanical robustness |
Bumps 6 ms 300 shocks 25 gn IEC 60068-2-27
|
Schneider TM3SAFL5R Safety Module for PLC TM2xx - 2 Functions, Category 3, Screw Terminals
- Brand: Schneider
- Product Code: TM3SAFL5R
- Availability: 1000
Tags: Schneider TM3SAFL5R, Safety Module, PLC TM2xx, Category 3, 2 Functions, Screw Terminals, Industrial Automation, Safety Solutions, Schneider Electric, Automation Safety