Schneider TM3SAK6RG Safety Module for PLC TM2xx Series – 3 Functions, Category 4, Spring Terminals
  • Brand: Schneider
  • Product Code: TM3SAK6RG
1000 |

Ex Tax: $0.00
Loading...

Description

Schneider TM3SAK6RG Safety Module for PLC TM2xx Series

Overview: The Schneider TM3SAK6RG Safety Module is a high-performance safety component designed to integrate seamlessly with Schneider's TM2xx PLC series. This advanced safety module provides crucial safety functions, ensuring operational integrity and compliance with Category 4 safety standards. Ideal for complex automation systems, the TM3SAK6RG module is engineered to deliver robust performance and reliability in safety-critical applications.

Key Features:

  • Safety Functions: The TM3SAK6RG Safety Module supports three essential safety functions, including:

    • Emergency Stop (E-Stop): Immediate and reliable shutdown of machinery in emergency situations.
    • Safety Gate Monitoring: Ensures that safety gates or protective barriers are properly closed before machinery resumes operation.
    • Muting Functions: Facilitates temporary bypass of safety functions for specific operations, maintaining safety without compromising productivity.
  • Category 4 Compliance: The module adheres to the highest safety standards, conforming to Category 4 of the ISO 13849-1 safety requirements. This ensures that the TM3SAK6RG provides maximum protection against potential hazards, minimizing risk and enhancing overall safety in industrial environments.

  • Spring Terminals: Equipped with spring-loaded terminals, the TM3SAK6RG facilitates secure and efficient wiring connections. The spring terminal design simplifies installation and maintenance, reducing wiring time and ensuring a stable electrical connection.

  • Compatibility: Specifically designed for use with the Schneider TM2xx PLC series, the TM3SAK6RG integrates effortlessly into existing systems. Its compatibility ensures a streamlined installation process and seamless operation with other Schneider automation components.

  • Robust Design: The TM3SAK6RG features a rugged and compact design, making it suitable for use in demanding industrial environments. Its durable construction is engineered to withstand harsh conditions and maintain optimal performance over time.

  • Easy Integration: The module supports straightforward configuration and integration with Schneider's PLC programming tools. Its user-friendly interface and documentation facilitate quick setup and programming, minimizing downtime and accelerating project deployment.

Applications: The Schneider TM3SAK6RG Safety Module is ideal for a wide range of industrial automation applications, including:

  • Manufacturing: Enhancing safety in production lines and machinery.
  • Processing: Ensuring secure operation in processing environments.
  • Material Handling: Protecting operators and equipment in material handling systems.

Technical Specifications:

  • Functionality: 3 safety functions
  • Safety Category: Category 4 (ISO 13849-1)
  • Connection Type: Spring terminals
  • Compatibility: Schneider TM2xx PLC series

Conclusion: The Schneider TM3SAK6RG Safety Module represents a crucial component in ensuring safety and compliance in industrial automation systems. With its advanced safety functions, Category 4 compliance, and user-friendly design, this module delivers exceptional performance and reliability for a wide range of applications. Integrate the TM3SAK6RG into your PLC system to enhance safety and operational efficiency.

Main
range of product
Modicon TM3 Safety
product or component type
Safety module
device short name
TM3SAK
safety module application
For emergency stop, switch, sensing mat/edges or safety light curtain monitoring
function of module
Emergency stop monitoring 1-channel wiring
Emergency stop monitoring 2-channel wiring
Monitoring of a movable guard
Multiple emergency stop monitoring 2-channel wiring
Sensing mat and edges monitoring
Monitoring of electro-sensitive protection equipment (ESPE) PNP/PNP
Proximity sensor monitoring PNP/PNP
Monitoring of electro-sensitive protection equipment (ESPE) PNP/NPN
Proximity sensor monitoring PNP/NPN
Monitoring of a movable guard with 2 switches and automatic start
safety level
Can reach PL e/category 4 EN/ISO 13849-1:2008
Can reach PL e/category 4 EN/ISO 13849-2:2012
Can reach SILCL 3 EN/IEC 62061:2005
Can reach SIL 3 EN/IEC 61508:2010
Complementary
safety reliability data
DC = 95 % EN/ISO 13849-1
PFHd = 5E-9 1/h IEC 61508-1 1 operation/hour DC-13 24 V DC 4 A
PFHd = 30E-9 1/h IEC 61508-1 60 operations/hour DC-13 24 V DC 1 A
MTTFd = 500 years EN/ISO 13849-1 1 operation/hour DC-13 24 V DC 4 A
MTTFd = 85 years EN/ISO 13849-1 60 operations/hour DC-13 24 V DC 1 A
SFF = 95 % IEC 61508-1
HFT = 1 IEC 61508-1
Type = A IEC 61508-1
synchronisation time between inputs
Unlimited
2 or 4 s depending of wiring configurable by software
connections - terminals
Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34
Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34
Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34
Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34
Captive spring terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34
Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals
Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals
Captive spring terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals
Captive spring terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals
output type
Relay instantaneous opening 3 NO potential free
number of safety circuits
3 NO (relay instantaneous opening)
maximum switching voltage
230 V utilisation category AC-15 at 50 Hz (relay instantaneous opening)
24 V utilisation category DC-13 (relay instantaneous opening)
[Us] rated supply voltage
24 V DC - 15...20 %
power consumption in W
0.2 W 5 V DC
3.6 W 24 V DC
input protection type
Internal, electronic
[Uc] control circuit voltage
24 V DC
cable distance between devices
30 m
breaking capacity
360 VA holding AC-15 B300 relay output
3600 VA inrush AC-15 B300 relay output
breaking capacity
4 A 24 V 50 ms DC-13 relay output
output thermal current
6 A per relay relay output
[Ith] conventional free air thermal current
18 A
associated fuse rating
4 A gG or gL relay output EN/IEC 60947-5-1
6 A fast blow relay output EN/IEC 60947-5-1
minimum output current
10 mA relay output
output voltage
10 V relay output
response time on input open
<= 40 ms
[Ui] rated insulation voltage
300 V 2 IEC 60647-5-1
[Uimp] rated impulse withstand voltage
4 kV III IEC 60647-5-1
current consumption
100 mA 24 V DC external supply
local signalling
8 LEDs green/red user
electrical connection
Spring terminal
product compatibility
Safety light curtains EN/IEC 61496-1 (type 4)
Sensing mat/edges EN 1760-1
standards
EN/ISO 13849-1:2008
EN/ISO 13849-2:2012
EN/IEC 62061:2005
EN/IEC 61508:2010
EN/IEC 60947-5-1:2010
EN/IEC 61131-2:2007
EN/IEC 60204-1:2005
EN/IEC 60204-1:2009/A1
IEC 61010-1:2010
EN 50581:2012
product certifications
ANSI Haz Loc Class 1 Division 2 (pending)
UL 61010-2-201
CSA 61010-2-201 (pending)
TÜV
CSA Haz Loc Class 1 Division 2 (pending)
RCM
EAC
marking
TÜV
RCM
EAC
REACH
EFUP 10
UL
CSA
CE
electromagnetic compatibility
Electrostatic discharge immunity test 8 kV air discharge conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test 6 kV contact discharge conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields 1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
Magnetic field at power frequency 30 A/m 50...60 Hz conforming to EN/IEC 61000-4-8
Electrical fast transient/burst immunity test 3 kV power lines (DC) conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test 2 kV I/O conforming to EN/IEC 61000-4-4
1.2/50 µs shock waves immunity test 1 kV power lines (DC) conforming to EN/IEC 61000-4-5
Conducted RF disturbances 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
Radiated emission 40 dBµV/m class A 24 V conforming to EN 55011
Radiated emission 47 dBµV/m class A 24 V conforming to EN 55011
mounting support
Wall mount using attached fasteners
Rail top hat type TH35-7.5 IEC 60715
Rail top hat type TH35-15 IEC 60715
height
94 mm
depth
73 mm
width
43.7 mm
product weight
0.19 kg

Environment
standards
EN 60204-1
EN/IEC 60947-1
EN/IEC 60947-5-1
EN/ISO 13850
EN 1088/ISO 14119
resistance to electrostatic discharge
6 kV on contact EN/IEC 61000-4-2
8 kV in air EN/IEC 61000-4-2
resistance to electromagnetic fields
10 V/m 80 MHz...1 GHz EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz EN/IEC 61000-4-3
1 V/m 2 GHz...3 GHz EN/IEC 61000-4-3
resistance to magnetic fields
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
resistance to fast transients
3 kV power lines (DC) EN/IEC 61000-4-4 DC
2 kV I/O lines EN/IEC 61000-4-4
surge withstand
1 kV power lines (DC) differential mode EN/IEC 61000-4-5 DC
1 kV power lines (DC) common mode EN/IEC 61000-4-5 DC
resistance to conducted disturbances
10 V 0.15...80 MHz EN/IEC 61000-4-6
electromagnetic emission
Radiated emissions 50 dBµV/m class A 24 V DC 30...230 Hz IEC 61131-3
Radiated emissions 57 dBµV/m class A 24 V DC 230...1000 Hz IEC 61131-3
ambient air temperature for operation
-10...55 °C horizontal installation
ambient air temperature for storage
-25...70 °C
relative humidity
10...95 % without condensation in operation
10...95 % without condensation in storage
IP degree of protection
IP20 EN/IEC 60529 terminals
pollution degree
2
operating altitude
0...2000 m
storage altitude
0...3000 m
vibration resistance
+/- 3.5 mm 5...150 Hz IEC 60068-2-6
shock resistance
15 gn 11 ms IEC 60068-2-27
mechanical robustness
Bumps 6 ms 300 shocks 25 gn IEC 60068-2-27