Schneider TM3TM3G Module TM3 - 2 Temperature Inputs and 1 Analog Output with Spring Connection
  • Brand: Schneider
  • Product Code: TM3TM3G
1000 |

Ex Tax: $0.00
Loading...

Description

Schneider TM3TM3G Module TM3 - 2 Temperature Inputs and 1 Analog Output with Spring Connection

Overview: The Schneider TM3TM3G Module TM3 is a high-performance expansion module designed for advanced industrial automation systems. Engineered to provide reliable and precise temperature monitoring and control, this module features 2 dedicated temperature inputs and 1 analog output, optimized for seamless integration into Schneider’s Modicon M221 and M241 PLC systems.

Key Features:

  • Dual Temperature Inputs: The TM3TM3G module is equipped with two temperature inputs, capable of interfacing with various temperature sensors such as RTDs (Resistance Temperature Detectors) or thermocouples. This functionality enables accurate temperature measurement and monitoring for a wide range of industrial applications.

  • Analog Output: The module includes a single analog output channel, providing flexibility in transmitting temperature data to other devices or systems. The output is designed for high precision and reliability, ensuring accurate data representation and control.

  • Spring Connection Technology: Featuring spring clamp connections, the TM3TM3G ensures secure and reliable wiring with minimal installation time. This technology reduces wiring errors and enhances connection stability, contributing to overall system robustness and longevity.

  • Compatibility and Integration: Designed for use with Schneider Electric’s Modicon PLCs, the TM3TM3G module integrates seamlessly into existing automation setups. It supports easy configuration and integration, reducing setup time and improving system efficiency.

  • Robust Performance: Built to withstand harsh industrial environments, the TM3TM3G module is engineered for durability and consistent performance. It is ideal for applications requiring high accuracy and reliability in temperature measurement and control.

Applications:

  • Manufacturing: Ideal for temperature monitoring in manufacturing processes, ensuring products meet quality standards and reducing the risk of overheating or cooling issues.

  • HVAC Systems: Suitable for HVAC applications where precise temperature control and monitoring are critical for system efficiency and performance.

  • Process Control: Enhances process control systems by providing accurate temperature data and reliable analog output for process adjustments and monitoring.

Specifications:

  • Temperature Inputs: 2 channels, compatible with RTDs and thermocouples
  • Analog Output: 1 channel
  • Connection Type: Spring clamp
  • Compatibility: Schneider Electric Modicon M221 and M241 PLCs
  • Operating Temperature Range: [Insert specific range]
  • Dimensions: [Insert dimensions]
  • Weight: [Insert weight]

Conclusion:

The Schneider TM3TM3G Module TM3 stands out for its precision, reliability, and ease of integration, making it an essential component for temperature measurement and control in modern industrial automation systems. Its advanced features and robust design ensure it meets the demands of various applications while simplifying installation and maintenance.

Keywords: Schneider TM3TM3G Module, temperature input module, analog output module, spring connection, Modicon M221, Modicon M241, industrial automation, temperature monitoring, HVAC systems, process control.

Main
range of product
Modicon TM3
product or component type
Input/output analog module
range compatibility
Modicon M221
Modicon M241
Modicon M251
analogue input number
2
analogue input type
Current, analogue input range: 4...20 mA
Current, analogue input range: 0...20 mA
Voltage, analogue input range: 0...10 V
Voltage, analogue input range: - 10...10 V
Thermocouple, analogue input range: - 200...1000 °C with thermocouple J
Thermocouple, analogue input range: - 200...1300 °C with thermocouple K
Thermocouple, analogue input range: 0...1760 °C with thermocouple R
Thermocouple, analogue input range: 0...1760 °C with thermocouple S
Thermocouple, analogue input range: 0...1820 °C with thermocouple B
Thermocouple, analogue input range: - 200...400 °C with thermocouple T
Thermocouple, analogue input range: - 200...1300 °C with thermocouple N
Thermocouple, analogue input range: - 200...800 °C with thermocouple E
Thermocouple, analogue input range: 0...2315 °C with thermocouple C
Ni 100/Ni 1000 temperature probe, analogue input range: - 60...180 °C
Pt 100 temperature probe, analogue input range: - 200...850 °C
Pt 1000 temperature probe, analogue input range: - 200...600 °C
analogue output number
1
analogue output type
4...20 mA current
0...20 mA current
0...10 V voltage
- 10...10 V voltage
Complementary
analogue input resolution
15 bits + sign
16 bits
permissible continuous overload
13 V voltage
40 mA current
input impedance
<= 50 Ohm current
>= 1 MOhm temperature probe
>= 1 MOhm thermocouple
>= 1 MOhm voltage
analogue output resolution
12 bits
LSB value
0.15 mV, analogue input: 0...10 V voltage
0.30 mV, analogue input: - 10...10 V voltage
0.30 µA, analogue input: 0...20 mA current
0.244 µA, analogue input: 4...20 mA current
0.1 °C temperature probe
2.44 mV, analogue output: 0...10 V voltage
4.88 mV, analogue output: - 10...10 V voltage
4.88 µA, analogue output: 0...20 mA current
3.91 µA, analogue output: 4...20 mA current
0.1 °C thermocouple
load type
Resistive
load impedance ohmic
1 kOhm voltage
300 Ohm current
stabilisation time
1 ms
conversion time
100 ms + 100 ms per channel + 1 controller cycle time for analogue input thermocouple
100 ms + 100 ms per channel + 1 controller cycle time for analogue input temperature probe
10 ms + 10 ms per channel + 1 controller cycle time for analogue input voltage/current
sampling duration
10 ms for analogue input voltage/current
100 ms for analogue input voltage/current
100 ms for analogue input thermocouple
100 ms for analogue input temperature probe
absolute accuracy error
+/- 0.1 % of full scale at 25 °C for analogue input voltage/current
+/- 0.1 % of full scale at 25 °C for analogue output voltage/current
+/- 0.1 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe
+/- 6 °C at 25 °C for thermocouple R, S 0...200 °C
+/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C
+/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple C 0...2315 °C
+/- 0.1 % of full scale at 25 °C for thermocouple R, S 200...1760 °C
+/- 0.1 % of full scale at 25 °C for thermocouple B 300...1820 °C
+/- 0.1 % of full scale at 25 °C for thermocouple K 0...1300 °C
+/- 0.1 % of full scale at 25 °C for thermocouple J 0...1000 °C
+/- 0.1 % of full scale at 25 °C for thermocouple E 0...800 °C
+/- 0.1 % of full scale at 25 °C for thermocouple T 0...400 °C
+/- 0.1 % of full scale at 25 °C for thermocouple N 0...1300 °C
temperature drift
+/- 0.006 %FS/°C
repeat accuracy
+/-0.5 %FS for input
+/- 0.4 %FS for output
non-linearity
+/- 0.01 %FS analog output
+/- 0.1 %FS analog input
output ripple
20 mV
cross talk
<= 1 LSB
[Us] rated supply voltage
24 V DC
supply voltage limits
20.4...28.8 V
type of cable
Twisted shielded pairs cable 30 m for input/output circuit
current consumption
55 mA at 24 V DC (no load) via external supply
55 mA at 5 V DC (no load) via bus connector
60 mA at 5 V DC (full load) via bus connector
80 mA at 24 V DC (full load) via external supply
local signalling
1 LED green for PWR
electrical connection
11 x 2.5 mm² removable spring terminal block with pitch 5.08 mm adjustment for inputs, outputs and supply
insulation
500 V AC between output and internal logic
500 V AC between input and internal logic
1500 V AC between input and supply
1500 V AC between output and supply
marking
CE
surge withstand
1 kV for power supply with common mode protection conforming to EN/IEC 61000-4-5
0.5 kV for power supply with differential mode protection conforming to EN/IEC 61000-4-5
1 kV for I/O with common mode protection conforming to EN/IEC 61000-4-5
0.5 kV for I/O with differential mode protection conforming to EN/IEC 61000-4-5
mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Plate or panel with fixing kit
height
90 mm
depth
70 mm
width
23.6 mm
product weight
0.1 kg

Environment
standards
EN/IEC 61131-2
EN/IEC 61010-2-201
resistance to electrostatic discharge
4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2
resistance to electromagnetic fields
10 V/m at 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m at 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m at 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
resistance to magnetic fields
30 A/m conforming to EN/IEC 61000-4-8
resistance to fast transients
1 kV I/O conforming to EN/IEC 61000-4-4
resistance to conducted disturbances
10 V at 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V at spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
electromagnetic emission
Radiated emissions, test level: 40 dBμV/m QP class A (10 m at 30...230 MHz) conforming to EN/IEC 55011
Radiated emissions, test level: 47 dBμV/m QP class A (10 m at 230...1000 MHz) conforming to EN/IEC 55011
immunity to microbreaks
10 ms
ambient air temperature for operation
-10...55 °C (horizontal installation)
-10...35 °C (vertical installation)
ambient air temperature for storage
-25...70 °C
relative humidity
10...95 % without condensation in operation
10...95 % without condensation in storage
IP degree of protection
IP20
pollution degree
2
operating altitude
0...2000 m
storage altitude
0...3000 m
vibration resistance
3.5 mm at 5...8.4 Hz with DIN rail mounting support
3 gn at 8.4...150 Hz with DIN rail mounting support
shock resistance
15 gn during 11 ms