Schneider TM3TM3G Module TM3 - 2 Temperature Inputs and 1 Analog Output with Spring Connection
Overview: The Schneider TM3TM3G Module TM3 is a high-performance expansion module designed for advanced industrial automation systems. Engineered to provide reliable and precise temperature monitoring and control, this module features 2 dedicated temperature inputs and 1 analog output, optimized for seamless integration into Schneider’s Modicon M221 and M241 PLC systems.
Key Features:
Dual Temperature Inputs: The TM3TM3G module is equipped with two temperature inputs, capable of interfacing with various temperature sensors such as RTDs (Resistance Temperature Detectors) or thermocouples. This functionality enables accurate temperature measurement and monitoring for a wide range of industrial applications.
Analog Output: The module includes a single analog output channel, providing flexibility in transmitting temperature data to other devices or systems. The output is designed for high precision and reliability, ensuring accurate data representation and control.
Spring Connection Technology: Featuring spring clamp connections, the TM3TM3G ensures secure and reliable wiring with minimal installation time. This technology reduces wiring errors and enhances connection stability, contributing to overall system robustness and longevity.
Compatibility and Integration: Designed for use with Schneider Electric’s Modicon PLCs, the TM3TM3G module integrates seamlessly into existing automation setups. It supports easy configuration and integration, reducing setup time and improving system efficiency.
Robust Performance: Built to withstand harsh industrial environments, the TM3TM3G module is engineered for durability and consistent performance. It is ideal for applications requiring high accuracy and reliability in temperature measurement and control.
Applications:
Manufacturing: Ideal for temperature monitoring in manufacturing processes, ensuring products meet quality standards and reducing the risk of overheating or cooling issues.
HVAC Systems: Suitable for HVAC applications where precise temperature control and monitoring are critical for system efficiency and performance.
Process Control: Enhances process control systems by providing accurate temperature data and reliable analog output for process adjustments and monitoring.
Specifications:
- Temperature Inputs: 2 channels, compatible with RTDs and thermocouples
- Analog Output: 1 channel
- Connection Type: Spring clamp
- Compatibility: Schneider Electric Modicon M221 and M241 PLCs
- Operating Temperature Range: [Insert specific range]
- Dimensions: [Insert dimensions]
- Weight: [Insert weight]
Conclusion:
The Schneider TM3TM3G Module TM3 stands out for its precision, reliability, and ease of integration, making it an essential component for temperature measurement and control in modern industrial automation systems. Its advanced features and robust design ensure it meets the demands of various applications while simplifying installation and maintenance.
Keywords: Schneider TM3TM3G Module, temperature input module, analog output module, spring connection, Modicon M221, Modicon M241, industrial automation, temperature monitoring, HVAC systems, process control.
range of product |
Modicon TM3
|
|
---|---|---|
product or component type |
Input/output analog module
|
|
range compatibility |
Modicon M221
Modicon M241 Modicon M251 |
|
analogue input number |
2
|
|
analogue input type |
Current, analogue input range: 4...20 mA
Current, analogue input range: 0...20 mA Voltage, analogue input range: 0...10 V Voltage, analogue input range: - 10...10 V Thermocouple, analogue input range: - 200...1000 °C with thermocouple J Thermocouple, analogue input range: - 200...1300 °C with thermocouple K Thermocouple, analogue input range: 0...1760 °C with thermocouple R Thermocouple, analogue input range: 0...1760 °C with thermocouple S Thermocouple, analogue input range: 0...1820 °C with thermocouple B Thermocouple, analogue input range: - 200...400 °C with thermocouple T Thermocouple, analogue input range: - 200...1300 °C with thermocouple N Thermocouple, analogue input range: - 200...800 °C with thermocouple E Thermocouple, analogue input range: 0...2315 °C with thermocouple C Ni 100/Ni 1000 temperature probe, analogue input range: - 60...180 °C Pt 100 temperature probe, analogue input range: - 200...850 °C Pt 1000 temperature probe, analogue input range: - 200...600 °C |
|
analogue output number |
1
|
|
analogue output type |
4...20 mA current
0...20 mA current 0...10 V voltage - 10...10 V voltage |
analogue input resolution |
15 bits + sign
16 bits |
|
---|---|---|
permissible continuous overload |
13 V voltage
40 mA current |
|
input impedance |
<= 50 Ohm current
>= 1 MOhm temperature probe >= 1 MOhm thermocouple >= 1 MOhm voltage |
|
analogue output resolution |
12 bits
|
|
LSB value |
0.15 mV, analogue input: 0...10 V voltage
0.30 mV, analogue input: - 10...10 V voltage 0.30 µA, analogue input: 0...20 mA current 0.244 µA, analogue input: 4...20 mA current 0.1 °C temperature probe 2.44 mV, analogue output: 0...10 V voltage 4.88 mV, analogue output: - 10...10 V voltage 4.88 µA, analogue output: 0...20 mA current 3.91 µA, analogue output: 4...20 mA current 0.1 °C thermocouple |
|
load type |
Resistive
|
|
load impedance ohmic |
1 kOhm voltage
300 Ohm current |
|
stabilisation time |
1 ms
|
|
conversion time |
100 ms + 100 ms per channel + 1 controller cycle time for
analogue input thermocouple
100 ms + 100 ms per channel + 1 controller cycle time for analogue input temperature probe 10 ms + 10 ms per channel + 1 controller cycle time for analogue input voltage/current |
|
sampling duration |
10 ms for analogue input voltage/current
100 ms for analogue input voltage/current 100 ms for analogue input thermocouple 100 ms for analogue input temperature probe |
|
absolute accuracy error |
+/- 0.1 % of full scale at 25 °C for analogue input
voltage/current
+/- 0.1 % of full scale at 25 °C for analogue output voltage/current +/- 0.1 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C +/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C +/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C +/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C +/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C +/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C +/- 0.1 % of full scale at 25 °C for thermocouple C 0...2315 °C +/- 0.1 % of full scale at 25 °C for thermocouple R, S 200...1760 °C +/- 0.1 % of full scale at 25 °C for thermocouple B 300...1820 °C +/- 0.1 % of full scale at 25 °C for thermocouple K 0...1300 °C +/- 0.1 % of full scale at 25 °C for thermocouple J 0...1000 °C +/- 0.1 % of full scale at 25 °C for thermocouple E 0...800 °C +/- 0.1 % of full scale at 25 °C for thermocouple T 0...400 °C +/- 0.1 % of full scale at 25 °C for thermocouple N 0...1300 °C |
|
temperature drift |
+/- 0.006 %FS/°C
|
|
repeat accuracy |
+/-0.5 %FS for input
+/- 0.4 %FS for output |
|
non-linearity |
+/- 0.01 %FS analog output
+/- 0.1 %FS analog input |
|
output ripple |
20 mV
|
|
cross talk |
<= 1 LSB
|
|
[Us] rated supply voltage |
24 V DC
|
|
supply voltage limits |
20.4...28.8 V
|
|
type of cable |
Twisted shielded pairs cable 30 m for input/output circuit
|
|
current consumption |
55 mA at 24 V DC (no load) via external supply
55 mA at 5 V DC (no load) via bus connector 60 mA at 5 V DC (full load) via bus connector 80 mA at 24 V DC (full load) via external supply |
|
local signalling |
1 LED green for PWR
|
|
electrical connection |
11 x 2.5 mm² removable spring terminal block with pitch 5.08 mm
adjustment for inputs, outputs and supply
|
|
insulation |
500 V AC between output and internal logic
500 V AC between input and internal logic 1500 V AC between input and supply 1500 V AC between output and supply |
|
marking |
CE
|
|
surge withstand |
1 kV for power supply with common mode protection conforming to
EN/IEC 61000-4-5
0.5 kV for power supply with differential mode protection conforming to EN/IEC 61000-4-5 1 kV for I/O with common mode protection conforming to EN/IEC 61000-4-5 0.5 kV for I/O with differential mode protection conforming to EN/IEC 61000-4-5 |
|
mounting support |
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715 Plate or panel with fixing kit |
|
height |
90 mm
|
|
depth |
70 mm
|
|
width |
23.6 mm
|
|
product weight |
0.1 kg
|
standards |
EN/IEC 61131-2
EN/IEC 61010-2-201 |
|
---|---|---|
resistance to electrostatic discharge |
4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2 |
|
resistance to electromagnetic fields |
10 V/m at 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m at 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 1 V/m at 2 GHz...3 GHz conforming to EN/IEC 61000-4-3 |
|
resistance to magnetic fields |
30 A/m conforming to EN/IEC 61000-4-8
|
|
resistance to fast transients |
1 kV I/O conforming to EN/IEC 61000-4-4
|
|
resistance to conducted disturbances |
10 V at 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V at spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
|
electromagnetic emission |
Radiated emissions, test level: 40 dBμV/m QP class A (10 m at
30...230 MHz) conforming to EN/IEC 55011
Radiated emissions, test level: 47 dBμV/m QP class A (10 m at 230...1000 MHz) conforming to EN/IEC 55011 |
|
immunity to microbreaks |
10 ms
|
|
ambient air temperature for operation |
-10...55 °C (horizontal installation)
-10...35 °C (vertical installation) |
|
ambient air temperature for storage |
-25...70 °C
|
|
relative humidity |
10...95 % without condensation in operation
10...95 % without condensation in storage |
|
IP degree of protection |
IP20
|
|
pollution degree |
2
|
|
operating altitude |
0...2000 m
|
|
storage altitude |
0...3000 m
|
|
vibration resistance |
3.5 mm at 5...8.4 Hz with DIN rail mounting support
3 gn at 8.4...150 Hz with DIN rail mounting support |
|
shock resistance |
15 gn during 11 ms
|