Schneider TMC2TI2 Cartridge M221 - Advanced Temperature Input Module for I/O Expansion
Unlock unparalleled precision and flexibility in your automation system with the Schneider TMC2TI2 Cartridge M221. This cutting-edge I/O extension module is engineered to enhance your control systems by providing two high-resolution temperature inputs, ensuring reliable data acquisition and process optimization.
Key Features:
Dual Temperature Inputs: The Schneider TMC2TI2 Cartridge M221 offers two independent temperature channels, capable of interfacing with a variety of temperature sensors. This feature allows for real-time monitoring and accurate temperature measurement critical for complex automation tasks.
Seamless Integration: Designed for use with Schneider Electric's M221 Logic Controllers, this module seamlessly integrates into your existing setup. The cartridge's plug-and-play functionality simplifies installation and configuration, reducing setup time and enhancing system efficiency.
High Accuracy and Reliability: Equipped with advanced analog-to-digital conversion technology, the TMC2TI2 ensures precise temperature readings with minimal error margins. This reliability is essential for applications where temperature control is crucial to process stability and product quality.
Robust I/O Extension: Expand your automation system's capabilities effortlessly. The TMC2TI2 serves as an I/O extension module, providing additional input options and enhancing the scalability of your control system. This modular approach allows for customized system expansion to meet evolving operational needs.
Industrial-Grade Design: Built to withstand the rigors of industrial environments, the Schneider TMC2TI2 Cartridge M221 features a durable design with robust protection against electrical noise and environmental factors. This ensures consistent performance and longevity in demanding applications.
User-Friendly Configuration: The module is designed with intuitive configuration options, accessible through Schneider Electric’s programming software. This user-centric approach facilitates easy setup and integration, allowing you to optimize your system with minimal effort.
Applications:
The Schneider TMC2TI2 Cartridge M221 is ideal for a wide range of industrial and commercial applications, including temperature monitoring in manufacturing processes, HVAC systems, and environmental control systems. Its versatility and precision make it a valuable addition to any automation setup requiring reliable temperature input and system expansion.
Optimize Your Automation System Today
Enhance the functionality and reliability of your control systems with the Schneider TMC2TI2 Cartridge M221. Whether you're upgrading an existing setup or designing a new automation solution, this advanced temperature input module offers the precision and flexibility needed to drive operational excellence.
Keywords: Schneider TMC2TI2 Cartridge M221, Temperature Input Module, I/O Extension, M221 Logic Controller, Industrial Temperature Sensors, Automation System Expansion, High Accuracy Temperature Measurement
range of product |
Modicon M221
|
|
---|---|---|
product or component type |
Analogue input cartridge
|
|
product compatibility |
Modicon M221C
|
|
analogue input number |
2
|
analogue input type |
Thermocouple, input range: - 200...1000 °C for thermocouple J
Thermocouple, input range: - 200...1300 °C for thermocouple K Thermocouple, input range: 0...1760 °C for thermocouple R Thermocouple, input range: 0...1760 °C for thermocouple S Thermocouple, input range: 0...1820 °C for thermocouple B Thermocouple, input range: - 200...400 °C for thermocouple T Thermocouple, input range: - 200...1300 °C for thermocouple N Thermocouple, input range: - 200...800 °C for thermocouple E Thermocouple, input range: 0...2315 °C for thermocouple C Temperature probe, input range: - 60...180 °C (Ni 100/Ni 1000) Temperature probe, input range: - 200...850 °C (Pt 100) Temperature probe, input range: - 200...600 °C (Pt 1000) |
|
---|---|---|
analogue input resolution |
14 bits
|
|
LSB value |
0.1 °C
|
|
sampling duration |
125 ms (thermocouple)
250 ms (temperature probe) |
|
absolute accuracy error |
+/- 0.1 % of full scale Pt 100/Pt 1000, Ni 100/ Ni 1000 25 °C
+/- 0.4 % of full scale thermocouple K - 200...0 °C 25 °C +/- 0.1 % of full scale thermocouple K 0...1300 °C 25 °C +/- 0.4 % of full scale thermocouple J - 200...0 °C 25 °C +/- 0.1 % of full scale thermocouple J 0...1000 °C 25 °C +/- 0.4 % of full scale thermocouple E - 200...0 °C 25 °C +/- 0.1 % of full scale thermocouple E 0...800 °C 25 °C +/- 0.4 % of full scale thermocouple T - 200...0 °C 25 °C +/- 0.1 % of full scale thermocouple T 0...400 °C 25 °C +/- 0.4 % of full scale thermocouple N - 200...0 °C 25 °C +/- 0.1 % of full scale thermocouple N 0...1300 °C 25 °C +/- 6 °C thermocouple R, S 0...200 °C 25 °C +/- 0.1 % of full scale thermocouple R, S 200...1760 °C 25 °C +/- 0.1 % of full scale thermocouple C 0...2315 °C 25 °C |
|
temperature drift |
+/- 0.02 %FS/°C
|
|
repeat accuracy |
+/- 0.5 %FS
|
|
non-linearity |
+/- 0.01 %FS
|
|
cross talk |
<= 1 LSB
|
|
type of cable |
Twisted shielded pairs cable
|
|
electrical connection |
2 screw terminal blocks (pitch 3.81 mm) 1.5 mm² 3 for inputs
|
|
cable distance between devices |
Twisted shielded pairs cable: 30 m for input
|
|
insulation |
Non-insulated between analogue input and internal logic
|
|
height |
41 mm
|
|
depth |
15 mm
|
|
width |
35 mm
|
|
product weight |
0.015 kg
|
|
input impedance |
>= 1 MOhm
|
immunity to microbreaks |
10 ms
|
---|