Schneider TSXAEY800C Analog Input Module - 8 High-Level Inputs, Current, Voltage - 12-Bit Precision
Optimize Your Automation System with Precision and Reliability
The Schneider TSXAEY800C Analog Input Module is engineered to elevate your automation processes with superior precision and reliability. Designed for advanced industrial applications, this high-performance module offers 8 high-level inputs for both current and voltage measurements, providing exceptional versatility and accuracy.
Key Features:
- 8 High-Level Inputs: Seamlessly integrate up to 8 input channels to monitor and control a wide range of analog signals with precision.
- Current and Voltage Measurement: Accommodate both current and voltage inputs, enhancing the module's flexibility to suit diverse applications.
- 12-Bit Resolution: Achieve high-resolution measurements with 12-bit precision, ensuring detailed and accurate data acquisition for critical processes.
- Robust Performance: Designed to withstand harsh industrial environments, the TSXAEY800C ensures consistent performance and long-term reliability.
- Compatibility: Ideal for use with Schneider's TSX Micro and TSX Premium PLC systems, ensuring seamless integration and operational efficiency.
Technical Specifications:
- Input Channels: 8
- Input Types: Current and Voltage
- Resolution: 12 Bits
- Input Range: (Specify the input range based on your model’s specifications)
- Accuracy: (Specify accuracy details based on your model’s specifications)
- Operating Temperature Range: (Specify temperature range if available)
- Dimensions: (Specify dimensions if relevant)
- Weight: (Specify weight if relevant)
Applications:
The Schneider TSXAEY800C Analog Input Module is ideal for a variety of applications, including process control, data acquisition, and system monitoring. Its high-resolution inputs make it suitable for environments requiring precise analog signal processing, such as manufacturing, energy management, and industrial automation.
Why Choose Schneider TSXAEY800C?
With the Schneider TSXAEY800C, you benefit from Schneider Electric’s renowned quality and innovation. This module is designed to deliver accurate and reliable analog input measurements, supporting your automation system's efficiency and performance. Enhance your control systems with a module that combines technical excellence with robust design.
Contact Us
For more information about the Schneider TSXAEY800C Analog Input Module or to request a quote, please contact our sales team. We are here to assist you in integrating this advanced module into your automation solutions.
range of product |
Modicon Premium Automation platform
|
|
---|---|---|
product or component type |
Analog input module
|
|
input level |
High level
|
|
analogue input number |
8
|
|
analogue input type |
Current 0...20 mA
Current 4...20 mA Voltage +/- 10 V Voltage 0...10 V Voltage 0...5 V Voltage 1...5 V |
|
analog/digital conversion |
12 bits
|
nominal read cycle time |
27 ms
|
|
---|---|---|
fast read cycle time |
3 ms + 3 ms x number of channels used
|
|
measurement error |
0.15 % of full scale 0...5 V 25 °C
0.15 % of full scale 1...5 V 25 °C 0.19 % of full scale +/- 10 V 25 °C 0.19 % of full scale 0...10 V 25 °C 0.22 % of full scale +/- 10 V 0...60 °C 0.22 % of full scale 0...10 V 0...60 °C 0.22 % of full scale 0...5 V 0...60 °C 0.22 % of full scale 1...5 V 0...60 °C 0.25 % of full scale 0...20 mA 25 °C 0.25 % of full scale 4...20 mA 25 °C 0.41 % of full scale 0...20 mA 0...60 °C 0.41 % of full scale 4...20 mA 0...60 °C |
|
isolation between channels and bus |
1000 Vrms
|
|
isolation between channels and ground |
1000 Vrms
|
|
isolation between channels |
Common point
|
|
common mode between channels |
None
|
|
input overvoltage protection |
-15...15 V at state 0 250 Ohm
-30...30 V at state 1 250 Ohm |
|
electrical connection |
1 connector SUB-D 25
|
|
overcurrent |
-30...30 mA at state 1 250 kOhm
|
|
marking |
CE
|
|
current consumption |
270 mA 5 V DC
|
|
module format |
Standard
|
|
product weight |
0.31 kg
|
standards |
IEC 1131
|
|
---|---|---|
product certifications |
ABS
BV DNV GL LR RINA RMRS |
|
ambient air temperature for operation |
0...60 °C
|
|
ambient air temperature for storage |
-25...70 °C
|
|
relative humidity |
10...95 % without condensation for operation
5...95 % without condensation for storage |
|
operating altitude |
0...2000 m
|
|
protective treatment |
Conformal coating Humiseal 1A33
TC |
|
IP degree of protection |
IP20
|
|
pollution degree |
2
|