Schneider VW3A4406 Additional EMC Input Filter - 3-Phase Supply - 90A
  • Brand: Schneider
  • Product Code: VW3A4406
1000 |

Ex Tax: $0.00
Loading...

Description

Schneider VW3A4406 Additional EMC Input Filter - 3-Phase Supply - 90A

Enhance the reliability and performance of your industrial electrical systems with the Schneider VW3A4406 Additional EMC Input Filter. Designed to provide superior electromagnetic compatibility (EMC) solutions, this filter is an essential component for ensuring that your equipment operates seamlessly and efficiently within a demanding electrical environment.

Key Features:

  • High Current Capacity: The VW3A4406 is engineered to handle 90A in a 3-phase supply configuration, making it ideal for robust industrial applications where substantial current management is crucial.

  • Effective EMC Protection: This additional EMC input filter significantly reduces electromagnetic interference (EMI) and radio-frequency interference (RFI), ensuring compliance with stringent EMC standards and protecting sensitive equipment from unwanted noise and disruptions.

  • Superior Filtering Performance: Designed to suppress high-frequency noise, the VW3A4406 improves the overall performance and reliability of your electrical systems, minimizing signal distortion and ensuring stable operation.

  • Durable Construction: Built to withstand the rigors of industrial environments, the filter features a rugged construction that ensures long-term durability and reliable performance under challenging conditions.

  • Versatile Application: Ideal for use with various Schneider electric drives and controllers, this filter seamlessly integrates into existing systems, enhancing their EMC performance without requiring extensive modifications.

  • Ease of Installation: The VW3A4406 is designed for straightforward installation, allowing for quick and efficient integration into your existing setup, reducing downtime and maintenance efforts.

Technical Specifications:

  • Type: Additional EMC Input Filter
  • Supply Type: 3-Phase
  • Current Rating: 90A
  • Compliance: Meets industry EMC standards for enhanced noise suppression
  • Construction: Robust and durable for industrial use

Applications:

The Schneider VW3A4406 is ideal for use in various industrial settings where high levels of electromagnetic interference need to be managed. It is particularly well-suited for applications involving large motors, drives, and other high-power electrical equipment where effective noise suppression is essential.

Why Choose Schneider VW3A4406?

Choosing the Schneider VW3A4406 Additional EMC Input Filter means investing in superior quality and performance. Schneider Electric's commitment to excellence ensures that you receive a product that not only meets but exceeds industry standards, providing you with peace of mind and operational efficiency.

Main
range of product
Altivar
product or component type
EMC input filter
range compatibility
Altivar 71
Altivar 212
Altivar 61
product compatibility
ATV71HD45N4
ATV71WD45N4
ATV71HD30M3X
ATV61HD45M3X
ATV71HD45M3X
ATV71HD37M3X
ATV61HD55N4
ATV71HD75N4
ATV71HD55N4
ATV61HD45N4
ATV71WD55N4
ATV61HD30M3X
ATV212HD55N4
ATV61HD75N4
ATV212HD30M3X
ATV61HD37M3X
ATV212HD75N4
ATV71WD75N4
product specific application
Radio interference input filter
[In] rated current
180 A
thermal losses
18 W for ATV21HD55N4
34 W for ATV21HD75N4
23.1 W for ATV21HD30M3X
58 W for ATV61/ATV71 variable speed drives
network number of phases
Three phase
Complementary
electrical connection
Terminal 150 mm² 300 kcmil
tightening torque
25 N.m
maximum earth leakage current
140 mA at 400 V 50 Hz
193 mA at 480 V 60 Hz
80 mA at 400 V 50 Hz
86.3 mA at 480 V 60 Hz
power supply voltage
380...500 V
200...240 V
tolerance
10 %
product weight
40 kg

Environment
IP degree of protection
IP20
IP41 (upper part)
relative humidity
0...93 % conforming to IEC 68-2-3
ambient air temperature for operation
-10...50 °C
ambient air temperature for storage
-40...65 °C
operating altitude
<= 1000 m without current derating
<= 1000 m without derating
1000...3000 m with current derating 1 % per 100 m
vibration resistance
1.5 mm peak to peak (f = 3...13 Hz) conforming to IEC 60068-2-6
1 gn (f = 13...150 Hz) conforming to IEC 60068-2-6
shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
standards
EN 133200
EN/IEC 61800-3