Schneider VW3A4709 EMC Radio Interference Input Filter
The Schneider VW3A4709 EMC Radio Interference Input Filter is a cutting-edge solution designed to mitigate electromagnetic interference (EMI) and radio frequency interference (RFI) in electrical systems. Crafted with precision engineering and advanced filtering technology, this input filter ensures optimal performance and reliability in demanding industrial environments.
Key Features:
Enhanced EMI/RFI Suppression: The VW3A4709 filter effectively suppresses electromagnetic and radio frequency interference, safeguarding sensitive electronic equipment from signal disruptions and ensuring consistent operation.
Compliance with Industry Standards: Engineered to meet stringent industry standards for electromagnetic compatibility (EMC), this input filter assures compliance with regulatory requirements, offering peace of mind to users across various sectors.
Wide Compatibility: With versatile compatibility, the VW3A4709 filter seamlessly integrates into diverse applications, including motor drives, variable frequency drives (VFDs), and other power electronics systems.
High Filtering Performance: Equipped with advanced filtering components, this filter provides exceptional noise attenuation across a broad frequency spectrum, maintaining signal integrity and system stability.
Robust Construction: Built to withstand harsh industrial conditions, the VW3A4709 filter features a rugged enclosure and high-quality components, ensuring durability and longevity in demanding environments.
Easy Installation: Designed for straightforward installation, this input filter facilitates quick integration into existing systems, minimizing downtime and streamlining maintenance procedures.
Applications:
Industrial Automation: Ideal for industrial automation systems, including machinery, robotics, and process control equipment, where reliable operation is crucial.
Commercial HVAC Systems: Ensures interference-free performance in heating, ventilation, and air conditioning (HVAC) systems, maintaining comfort and efficiency in commercial buildings.
Renewable Energy Systems: Suitable for use in renewable energy applications such as solar inverters and wind turbines, where clean power delivery is essential for maximum energy yield.
Technical Specifications:
- Voltage Rating: [Insert Voltage Rating]
- Frequency Range: [Insert Frequency Range]
- Current Rating: [Insert Current Rating]
- Insulation Class: [Insert Insulation Class]
- Operating Temperature: [Insert Operating Temperature Range]
- Connection Type: [Insert Connection Type]
- Dimensions: [Insert Dimensions]
- Certifications: [Insert Certifications - e.g., CE, UL]
Conclusion:
The Schneider VW3A4709 EMC Radio Interference Input Filter sets a new standard for EMI/RFI mitigation, offering unparalleled performance, reliability, and compatibility. Whether you're in industrial automation, HVAC, or renewable energy sectors, this filter ensures uninterrupted operation and optimal system performance. Invest in the VW3A4709 filter today and experience the difference it makes in your applications.
Keywords for SEO:
- EMC Input Filter
- Radio Interference Filter
- EMI/RFI Suppression
- Industrial Automation Filter
- Schneider VW3A4709 Filter
- Electrical Noise Attenuation
- Compliance with EMC Standards
- Industrial Input Filter
- High-Performance Filtering Solution
For more information or to purchase the Schneider VW3A4709 EMC Radio Interference Input Filter, contact us today.
Schneider VW3A4709 EMC radio interference input filter - for variable speed drive - 3-phase supply
range of product |
Altivar
|
|
---|---|---|
product or component type |
EMC input filter
|
|
range compatibility |
Altivar Process ATV600
Altivar Process ATV900 |
|
product compatibility |
ATV630 wall mount, at 110 kW, 380...480 V
ATV630 wall mount, at 132 kW, 380...480 V ATV630 wall mount, at 55 kW, 200...240 V ATV930 wall mount, at 110 kW, 380...480 V ATV930 wall mount, at 132 kW, 380...480 V ATV930 wall mount, at 55 kW, 200...240 V |
|
product specific application |
Radio interference input filter
|
|
[In] rated current |
240 A
|
|
network number of phases |
Three phase
|
electrical connection |
Copper bar M10
|
|
---|---|---|
motor cable length |
<= 150 m shielded motor cable 4 kHz conforming to EN/IEC 61800-3
category C2, 380...480 V
<= 300 m shielded motor cable 4 kHz conforming to EN/IEC 61800-3 category C3, 380...480 V <= 150 m shielded motor cable 4 kHz conforming to EN/IEC 61800-3 category C2, 200...240 V <= 300 m shielded motor cable 4 kHz conforming to EN/IEC 61800-3 category C3, 200...240 V <= 50 m shielded motor cable 4 kHz conforming to EN/IEC 61800-3 category C1, 200...240 V |
|
maximum earth leakage current |
27.8 mA at 400 V 50 Hz TN
27.8 mA at 400 V 50 Hz TT |
|
power supply voltage |
200...240 V
380...480 V |
|
tolerance |
10 %
|
|
mechanical robustness |
Shocks conforming to IEC 60721-3-3 class 3M4
Vibrations conforming to IEC 60721-3-3 class 3M4 |
|
width |
260 mm
|
|
height |
520 mm
|
|
depth |
117 mm
|
|
product weight |
15 kg
|
IP degree of protection |
IP00
|
|
---|---|---|
relative humidity |
5...95 % without condensation conforming to IEC 61800-5-1
|
|
ambient air temperature for operation |
50...60 °C with current derating 1.5 % per °C
-10...50 °C without current derating |
|
ambient air temperature for storage |
-40...70 °C
|
|
operating altitude |
0...1000 m without current derating
1000...4000 m with current derating 1 % per 100 m |
|
standards |
EN/IEC 61800-3
|